Replacement unit for the Thermal Care TSE Series Water-Cooled

TSE Series Water-Cooled

Thermal Care's scroll-compressor central chiller on tower water: 11 to 256 tons, single or dual circuit, with an integral tank and pumps as an option.

PRODUCT TYPE CAPACITY MODELS
Central Chiller Water-Cooled Central 11 to 256 Tons 22

Specifications


Configuration & Size

Capacity:
11 to 256 Tons at 50°F
Models:
22 part numbers
Compressor:
Scroll, 2 or 3 per circuit
Process Connections:
1-1/2 to 6 in
Refrigerant:
R-454B, R-410A

Construction

  • Scroll compressors, 2 or 3 per circuit
  • Cleanable condensers, removable heads
  • Stainless brazed plate evaporators
  • Electronic expansion valves
  • Optional integral tank and pumps

Ratings

  • Rated at 50°F set point, 60°F return
  • 85°F condenser water
  • R-410A or R-454B
  • Power: 460/3/60 published

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.

TSE Water-Cooled Central Chillers, 11 to 256 Tons

The Central Chiller for a Glycol Plant

Twenty-two models, single or dual circuit. The TSEW010S to TSEW120S carry one refrigeration circuit and the TSEW020D to TSEW240D two. Scroll compressors run two to a circuit, three on the 100 and 120-ton single-circuit units and on the 200 and 240-ton dual-circuit units, into stainless steel brazed plate evaporators.

Capacity is published at a 50°F set point, 60°F return and 85°F condenser water, from 11 tons on the TSEW010S to 256 tons on the TSEW240D, on R-410A or R-454B. Unlike the TC line, the set point range runs 20 to 80°F.

The condenser is cleanable. Water-cooled condensers are frame-mounted with removable heads, with a condenser water regulating valve. Process and condenser connections run from 1-1/2 inch on the smallest to 6 inch on the largest.

The tank is an option, with two sizes. Most sizes can be ordered with a standard reservoir of 275 to 1,000 gallons and process and chiller pumps, or a high-flow reservoir of 400 to 1,000 gallons with larger pumps. The 100 and 120-ton single-circuit and the 200 and 240-ton units have no tank option listed.



industrial refrigeration machinery room with piping and vessels

Scroll compressors, cleanable water-cooled condensers and a modular design that grows past 1,000 tons.

Request a Quote

TSE Series Water-Cooled Applications

Plastics plant headers
Plastics plant headers
Glycol process loops
Glycol process loops
Dual-circuit redundancy
Dual-circuit redundancy
Tower-water plants
Tower-water plants

schematic of the TSE series Water-Cooled circuit, showing where the process fluid and the condenser heat go

Modular, and Built to Be Combined

A TSE is a building block. Thermal Care allows up to six chillers and twelve refrigeration circuits in one system, over 1,000 tons, and the single-circuit units fit through a standard 36-inch door. That makes a failed TSE in a multi-chiller plant a unit swap, not a plant rebuild, provided the new chiller matches the header, the controls and the condenser water.

The S and D versions are worth separating in a replacement. A dual-circuit TSEW060D is published at 65 tons against 69 for the single-circuit TSEW060S, but it keeps half its compressors running if one circuit trips. If the plant was built around that redundancy, the replacement should keep it. The tonnage and capacity guide covers how to count the load across several chillers.

Every part-number page below names the Temptek water-cooled chilling module we supply in its place, with the same number of circuits and sized to cover the published 50°F capacity. The TSEW200D and TSEW240D are beyond any single Temptek unit, so their pages point to the add-on module range on our sister site.
Call and talk it through with an engineer: 1-805-484-2992

Selection Notes on TSE Water-Cooled Chillers

For most process plants, yes: the dual-circuit TSEW060D is listed at 65 tons and the single-circuit TSEW060S at 69, about 6% less for the D, and in exchange one circuit can trip without taking the plant to zero. With a circuit down, the D still carries roughly half its capacity, around 32 tons, enough to hold many processes at a reduced rate; the S has nothing left. The S makes sense where a second chiller already covers a failure. Whichever the plant was built on, the MW module we supply keeps the same number of circuits, so tell us whether that redundancy is part of your operating plan.

When the process flow is higher than the chiller's own evaporator flow, or the loop needs more buffer: the TSEW060S lists 450 gallons standard or 650 gallons high-flow, about 44% more volume, with larger pumps on the high-flow version. A plant header serving many molds often draws more than the chiller circulates, and the larger tank and pumps decouple the two flows. If the existing TSEW has the high-flow tank, that is a clue the process flow is large; measure it. The MW module we supply is refrigeration only, so whichever tank you have is matched in the pump-tank station.

As a regulating valve that sits wide open and a head pressure that creeps up season by season, until the unit trips on the hottest afternoon. The valve opens further to hold head pressure as scale builds, so near full open on a mild day is the early warning. Pull the removable heads, clean the tubes and treat the water; the replacement sees the same water.

About 614 GPM on water at a 10°F rise across its published 256 tons: 256 x 12,000 is 3,072,000 BTU/hr, which at 500 x 10 per GPM comes to 614.4 GPM. With glycol the flow is higher, and at a tighter 8°F rise the same load needs about 768 GPM, so the rise the plant actually runs matters as much as the tonnage when the header is reviewed. No single Temptek unit reaches the TSEW240D or the TSEW200D, so they are covered by add-on modules sized together to the load, and those modules together have to pass that flow into the same header. Check the header and the pump-tank station at that flow before the modules are laid out; the 6-inch connections on the old chiller show the size the plant was piped for.

The TSEW010S takes the MW-10-C at 11.5 tons against its published 11, and the dual-circuit TSEW050D takes the MW-60-CC at 60 tons against 54. That is half a ton of margin on the smallest size and 6 tons on the TSEW050D, so the small one in particular has no room for a load that has grown since it was installed. The MW is a water-cooled chilling module with the same circuit count as the unit it replaces, and it is refrigeration only, working with a pump-tank station. If your TSEW has the integral tank, that duty moves to the station.