| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Air-Cooled Scroll Chiller | Air-Cooled | 140 Tons nominal | R-454B |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ACS140 as shown on this page.
The Trane ACS140 is the 140-ton nominal size of the Ascend ACS air-cooled chiller, with 4 scroll compressors on two refrigerant circuits and 8 condenser fans. Trane lists an evaporator flow range of 168 to 504 GPM and capacity steps of 21-43-71-100 percent, on R-454B. The catalog gives the size as nominal tons; the rated capacity is on the nameplate and in Trane's selection data. Replacement: we supply the Temptek TTOACS-210D-MZC-2P, a dual-zone outdoor air-cooled packaged chiller rated 188 tons at 50°F, against the 140 tons Trane publishes for this unit at its nominal size (AHRI conditions, 44°F leaving water). Temptek rates at 50°F, so the 44°F figure is matched on Temptek's published 40°F capacity multiplier of 0.80, which leaves the pick some margin; we confirm it at your set point.
Specifications sourced from Trane's published product catalogs CG-PRC017AA-EN and AC-PRC002K-EN (tranetechnologies.com), October 2026. Trane, CGAM, Ascend and Symbio are trademarks of Trane Technologies; referenced here for cross-reference only. Sizes are Trane's nominal tons; rated performance comes from Trane's selection data. Confirm against the unit nameplate before ordering.