The York YLAA in two refrigerants, 39 to 222 nominal tons

Contact us

The York Scroll Chiller That Cools Glycol

The York YLAA in two refrigerants, 45 part numbers, from 39 to 222 nominal tons. Each one is listed with its published rating and the unit we supply in its place.

York chillers are built by Johnson Controls, mostly for comfort cooling. The line plants ask us about is the YLAA, an air-cooled scroll chiller of 40 to 230 tons with a brazed plate evaporator, because Johnson Controls states it can cool glycol down to 10°F with the optional low temperature glycol kit. The Style B 60 Hz engineering guide lists every model twice: once on R-410A (model suffix E) and once on R-454B (suffix J), with a nominal rating in tons, the input kW, EER and IPLV for each. Those ratings are certified under AHRI 550/590.

  • Standard efficiency (S): eight sizes, 70 to 170 nominal tons.
  • High efficiency (H): thirteen sizes, 39 to 222 nominal tons.
  • R-410A models end in E; R-454B models end in J.
  • The R-454B ratings run up to about 2 percent below R-410A.
  • Four, five or six scroll compressors on two circuits.
  • Leaving liquid 40 to 55°F, or to 10°F with the glycol kit.
45
YLAA part numbers in two refrigerants
39 to 222 tons
nominal sizes, both refrigerant versions
R-454B
refrigerant on 24 of the part numbers
10°F
lowest glycol temperature, with the kit
Replacement unit for the York YLAA Series

YLAA Series:

Air-Cooled Scroll, R-410A

  • 21 part numbers
  • 39.5 to 221.7 nominal tons
  • Glycol to 10°F with kit
Replacement unit for the York YLAA R-454B Series

YLAA R-454B Series:

Air-Cooled Scroll, R-454B

  • 24 part numbers
  • 39.0 to 221.7 nominal tons
  • Glycol to 10°F with kit

Reading a YLAA Model Number

YLAA0125HE46. YL is a York chiller, the first A air-cooled, the second A the design series. The four digits are the unit number, close to the nominal tons: an 0125 high-efficiency unit is rated 118.0 tons on R-410A.

The two letters after the digits. S is standard efficiency and H is high efficiency; E is R-410A and J is R-454B. So a YLAA0125HE and a YLAA0125HJ are the same frame on different refrigerants.

The voltage code follows. 17 is 200 V, 28 is 230 V, 40 is 380 V, 46 is 460 V and 58 is 575 V, all three-phase 60 Hz. The tonnage and capacity guide explains how a nominal rating relates to working capacity.

Replacing a York YLAA on a Process Loop

We do not sell York equiptment. We supply new Temptek process chillers, and every York part-number page names the Temptek unit we would put in its place. York's nominal rating is an AHRI figure at 44°F leaving water and 95°F ambient; Temptek rates at 50°F and 95°F. A chiller makes less at 44°F than at 50°F, so the York tons are matched on Temptek's published 40°F multiplier of 0.80: the York figure divided by 0.80, which leaves the pick some margin.

From about 150 nominal tons up, the divided figure passes the largest single Temptek outdoor chiller, and those pages point to the add-on module range on our sister site. If the YLAA runs a low-temperature glycol loop, the working capacity is well below nominal, so send the set point and glycol mix with the model and serial.
Call and talk it through with an engineer: 1-805-484-2992

Specifications sourced from Johnson Controls' published YLAA engineering guide, Form 150.72-EG6 (docs.johnsoncontrols.com), October 2026. York and YLAA are trademarks of Johnson Controls; referenced here for cross-reference only. Capacities are the guide's nominal ratings under AHRI 550/590. Confirm against the unit nameplate before ordering.

Before You Order

refrigerant cylinders and gauges for a chiller refrigerant change

REPLACE • REFRIGERANT

Refrigerant Phase-Out

Older units in the field may still run R-22 or R-410A. What the refrigerant change means for service, retrofit and replacement.

+ Learn More
chiller swap-out checklist on a clipboard in a plant room

REPLACE • INSTALL

Swap-Out Checklist

Rigging, electrical, piping and start-up items to settle before the old chiller comes out of service.

+ Learn More
aging outdoor chiller showing wear on a concrete pad

REPLACE • CONDITION

Signs You Need a New Chiller

Short cycling, rising amps, a tank that will not pull down: the symptoms that say the old unit is near the end.

+ Learn More