The York YLAA in two refrigerants, 45 part numbers, from 39 to 222 nominal tons. Each one is listed with its published rating and the unit we supply in its place.
York chillers are built by Johnson Controls, mostly for comfort cooling. The line plants ask us about is the YLAA, an air-cooled scroll chiller of 40 to 230 tons with a brazed plate evaporator, because Johnson Controls states it can cool glycol down to 10°F with the optional low temperature glycol kit. The Style B 60 Hz engineering guide lists every model twice: once on R-410A (model suffix E) and once on R-454B (suffix J), with a nominal rating in tons, the input kW, EER and IPLV for each. Those ratings are certified under AHRI 550/590.
YLAA0125HE46. YL is a York chiller, the first A air-cooled, the second A the design series. The four digits are the unit number, close to the nominal tons: an 0125 high-efficiency unit is rated 118.0 tons on R-410A.
The two letters after the digits. S is standard efficiency and H is high efficiency; E is R-410A and J is R-454B. So a YLAA0125HE and a YLAA0125HJ are the same frame on different refrigerants.
The voltage code follows. 17 is 200 V, 28 is 230 V, 40 is 380 V, 46 is 460 V and 58 is 575 V, all three-phase 60 Hz. The tonnage and capacity guide explains how a nominal rating relates to working capacity.
We do not sell York equiptment. We supply new Temptek process chillers, and every York part-number page names the Temptek unit we would put in its place. York's nominal rating is an AHRI figure at 44°F leaving water and 95°F ambient; Temptek rates at 50°F and 95°F. A chiller makes less at 44°F than at 50°F, so the York tons are matched on Temptek's published 40°F multiplier of 0.80: the York figure divided by 0.80, which leaves the pick some margin.
From about 150 nominal tons up, the divided figure passes the largest single Temptek outdoor chiller, and those pages point to the add-on module range on our sister site. If the YLAA runs a low-temperature glycol loop, the working capacity is well below nominal, so send the set point and glycol mix with the model and serial.
Call and talk it through with an engineer: 1-805-484-2992
Specifications sourced from Johnson Controls' published YLAA engineering guide, Form 150.72-EG6 (docs.johnsoncontrols.com), October 2026. York and YLAA are trademarks of Johnson Controls; referenced here for cross-reference only. Capacities are the guide's nominal ratings under AHRI 550/590. Confirm against the unit nameplate before ordering.
Older units in the field may still run R-22 or R-410A. What the refrigerant change means for service, retrofit and replacement.
+ Learn More
Rigging, electrical, piping and start-up items to settle before the old chiller comes out of service.
+ Learn More
Short cycling, rising amps, a tank that will not pull down: the symptoms that say the old unit is near the end.
+ Learn More