The current-refrigerant YLAA: the same Style B frames on R-454B, 39.0 to 221.7 nominal tons.
| PRODUCT | TYPE | CAPACITY | MODELS |
|---|---|---|---|
| Air-Cooled Scroll Chiller | Packaged, Low-GWP | 39.0 to 221.7 nominal tons | 24 |
Specifications sourced from Johnson Controls' published YLAA engineering guide, Form 150.72-EG6 (docs.johnsoncontrols.com), October 2026. York and YLAA are trademarks of Johnson Controls; referenced here for cross-reference only. Capacities are the guide's nominal ratings under AHRI 550/590. Confirm against the unit nameplate before ordering.
Twenty-four models. Eight standard-efficiency SJ models, thirteen high-efficiency HJ models and three ZJ models.
Slightly lower ratings. A YLAA0125HJ is rated 116.2 tons against 118.0 for the R-410A YLAA0125HE, at a higher EER of 10.5.
Smaller charges. The R-454B charge per circuit is lower: 59 and 55 lb on the 0125HJ against 70 and 66 lb on the 0125HE.
The ZJ models. The 0070ZJ, 0100ZJ and 0155ZJ carry larger charges and a 0°F minimum air temperature; the guide does not define the Z.
Hermetic scroll compressors on two R-454B circuits, a brazed plate evaporator and single-row condenser coils.
Request a Quote
R-454B is mildly flammable, class A2L, and the guide lists UL 60335-2-40 refrigerant detector requirements among the approvals. That affects where the chiller can sit. The indoor vs outdoor installation guide covers siting.
Every part-number page below names the Temptek unit we supply in its place, sized from York's nominal tons on Temptek's 0.80 multiplier at 40°F, or points to the add-on module range where the size is past a single chiller.