| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Air-Cooled Scroll Chiller | Air-Cooled | 94.6 Tons nominal | R-454B |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n YLAA0100ZJ as shown on this page.
The York YLAA0100ZJ is a Z-coded YLAA Style B air-cooled scroll chiller on R-454B, with 5 scroll compressors on two refrigerant circuits and a brazed plate evaporator. Johnson Controls lists a nominal rating of 94.6 tons at 113.8 kW input, an EER of 10.0 and an IPLV of 14.9. It is 142.7 inches long and weighs 6,152 lb operating. Replacement: we supply the Temptek TTOACS-150D-MZC-2P, an outdoor air-cooled packaged chiller rated 145.8 tons at 50°F, against the 94.6 tons York publishes for this unit at its nominal AHRI rating (44°F leaving water). Temptek rates at 50°F, so the 44°F figure is matched on Temptek's published 40°F capacity multiplier of 0.80, which leaves the pick some margin; we confirm it at your set point.
Specifications sourced from Johnson Controls' published YLAA engineering guide, Form 150.72-EG6 (docs.johnsoncontrols.com), October 2026. York and YLAA are trademarks of Johnson Controls; referenced here for cross-reference only. Capacities are the guide's nominal ratings under AHRI 550/590. Confirm against the unit nameplate before ordering.