1-805-484-2992

Quotes - Sizing - Sales

YLAA0065HE

York
Product Type Capacity Refrigerant
Air-Cooled Scroll Chiller Air-Cooled 62.3 Tons nominal R-410A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n YLAA0065HE as shown on this page.

Replacement chiller for the York YLAA0065HE

Description

The York YLAA0065HE is a high efficiency YLAA Style B air-cooled scroll chiller on R-410A, with 5 scroll compressors on two refrigerant circuits and a brazed plate evaporator. Johnson Controls lists a nominal rating of 62.3 tons at 71.9 kW input, an EER of 10.4 and an IPLV of 16.3. It is 100.2 inches long and weighs 3,748 lb operating. Replacement: we supply the Temptek TTOACS-100D-MZC-2P, an outdoor air-cooled packaged chiller rated 84.6 tons at 50°F, against the 62.3 tons York publishes for this unit at its nominal AHRI rating (44°F leaving water). Temptek rates at 50°F, so the 44°F figure is matched on Temptek's published 40°F capacity multiplier of 0.80, which leaves the pick some margin; we confirm it at your set point.

Product Overview

Part Number:
YLAA0065HE
Manufacturer:
York
Series:
YLAA Series
Replacement Unit:
Temptek TTOACS-100D-MZC-2P

Published Capacity

Nominal Rating:
62.3 tons
Input Power:
71.9 kW
EER:
10.4
IPLV:
16.3
Rating Basis:
AHRI Standard 550/590
Leaving Liquid:
40 to 55°F standard; to 10°F with the low temperature glycol kit
Air on Condenser:
-10 to 125°F (low ambient kit below 30°F)

Configuration & Specifications

Compressors:
5 hermetic scroll (3/2 per circuit)
Nominal Tons per Compressor:
Circuit 1: 13; circuit 2: 15
Refrigerant Circuits:
2
Refrigerant:
R-410A
Refrigerant Charge (circuit 1 / 2):
38/38 lb
Condenser Fans (circuit 1 / 2):
2/2, 2 HP
Total Airflow:
60,000 cfm

Evaporator

Type:
Brazed plate
Water Volume:
5.4 gallons
Minimum Water Flow:
60 GPM
Maximum Water Flow:
285 GPM
Max Water Side Pressure:
150 psig

Electrical

Voltages Offered:
200, 230, 380, 460 or 575 V / 3 phase / 60 Hz

Connections

Water Connections:
3 in

Dimensions & Weight

Length:
100.2 in
Width:
88 in
Height:
94.2 in
Shipping Weight:
3,704 lb
Operating Weight:
3,748 lb

Specifications sourced from Johnson Controls' published YLAA engineering guide, Form 150.72-EG6 (docs.johnsoncontrols.com), October 2026. York and YLAA are trademarks of Johnson Controls; referenced here for cross-reference only. Capacities are the guide's nominal ratings under AHRI 550/590. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales