1-805-484-2992

Quotes - Sizing - Sales

PAC1000D-S

Drake
Product Type Capacity Refrigerant
Packaged Chiller Air-Cooled Packaged 86.5 Tons @ 55°F R407C or R404A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PAC1000D-S as shown on this page.

Replacement chiller for the Drake PAC1000D-S

Description

The Drake PAC1000D-S is a 100 hp dual-circuit semi-hermetic packaged air-cooled chiller, from the PAC Semi-Hermetic line. Drake publishes a capacity table for it rather than a single rating: 86.5 tons at 55°F leaving fluid and 95°F ambient on R407C, at an EER of 9.1. The same column runs from 39.9 tons at 20°F to 103 tons at 65°F. It is offered on R407C for a 10°F to 55°F suction range and R404A for a -10°F to 45°F suction range. Replacement: we supply the Temptek TTI-100A, an air-cooled central chiller rated 90 tons at 50°F, against the 86.5 tons Drake publishes for this unit at 55°F leaving fluid and 95°F ambient on R407C. Drake's table has no 50°F row for this unit, so its 55°F figure is used; a chiller makes at least as much at a warmer set point, so the pick keeps a margin at 50°F.

Product Overview

Part Number:
PAC1000D-S
Manufacturer:
Drake
Replacement Unit:
Temptek TTI-100A

Published Capacity

Cooling Capacity:
86.5 tons at 55°F leaving fluid
Rating Point Used:
55°F leaving fluid, 95°F ambient, R407C
Capacity at 20°F Leaving Fluid:
39.9 tons
Capacity at 35°F Leaving Fluid:
57.3 tons
Capacity at 45°F Leaving Fluid:
71.3 tons
Capacity at 65°F Leaving Fluid:
103 tons
R404A Low-Temperature Range:
33.3 tons at 0°F to 93.3 tons at 55°F
R407C Suction Range:
10°F to 55°F
R404A Suction Range:
-10°F to 45°F

Configuration & Specifications

Horsepower:
100 HP
Compressor:
Semi-Hermetic
Circuits:
Dual
Condenser:
Air-Cooled
Refrigerant:
R407C or R404A

Electrical

Voltage Options:
208-230 V three-phase / 460 V three-phase / 575 V three-phase
Frequency:
60 Hz

Connections

Process Connections:
4 in F-NPT

Dimensions & Weight

Dimensions (L x W x H):
175 x 88 x 84 in
Weight:
6,400 lbs

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales