| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Packaged Chiller | Water-Cooled Packaged | 51.3 Tons @ 50°F | R407C |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PWC600D as shown on this page.
The Drake PWC600D is a 50 hp dual-circuit scroll packaged water-cooled chiller, from the PWC / PWCT Scroll line. Drake publishes a capacity table for it rather than a single rating: 51.3 tons at 50°F leaving fluid and 105°F condensing temperature on R407C, at an EER of 15.9. The same column runs from 37.2 tons at 35°F to 70.1 tons at 65°F. Drake lists two ZR300KCE compressors of 25 hp each. Replacement: we supply the Temptek TTI-60W, a water-cooled central chiller rated 60 tons at 50°F, against the 51.3 tons Drake publishes for this unit at 50°F leaving fluid and 105°F condensing temperature on R407C. Drake rates this water-cooled table by condensing temperature rather than water temperature; the 105°F column is the usual condensing point on 85°F tower water, and we confirm it with your water temperature. It is a central chiller rather than a portable, because the largest Temptek water-cooled portable, the CG-40W (40 tons), falls short of this figure.
Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.