| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Packaged Chiller | Water-Cooled Packaged | 70.8 Tons @ 55°F | R407C |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PWC630Q-Z as shown on this page.
The Drake PWC630Q-Z is a 60 hp tandem-circuit tandem scroll packaged water-cooled chiller, from the PWC / PWCT Scroll line. Drake publishes a capacity table for it rather than a single rating: 70.8 tons at 55°F leaving fluid and 85°F entering condenser water on R407C, at an EER of 849. The same column runs from 31.4 tons at 20°F to 78.5 tons at 60°F. Drake lists four ZR190KCE compressors of 15 hp each. Replacement: we supply the Temptek TTI-80W, a water-cooled central chiller rated 85.2 tons at 50°F, against the 70.8 tons Drake publishes for this unit at 55°F leaving fluid and 85°F entering condenser water on R407C. Drake's table has no 50°F row for this unit, so its 55°F figure is used; a chiller makes at least as much at a warmer set point, so the pick keeps a margin at 50°F. It is a central chiller rather than a portable, because the largest Temptek water-cooled portable, the CG-40W (40 tons), falls short of this figure.
Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.