| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Packaged Chiller | Water-Cooled Packaged | 4.8 Tons @ 55°F | R407C or R404A |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PWCT48S as shown on this page.
The Drake PWCT48S is a 5 hp single-circuit scroll packaged water-cooled chiller with a tank, from the PWC / PWCT Scroll line. Drake publishes a capacity table for it rather than a single rating: 4.8 tons at 55°F leaving fluid and 105°F condensing temperature on R407C, at an EER of 14.9. The same column runs from 3.6 tons at 40°F to 6.4 tons at 70°F. It is offered on R407C for a 25°F to 55°F suction range and R404A for a -10°F to 45°F suction range. Drake lists one ZB38KCE compressor of 5 hp. Its tank holds 60 gallons. Replacement: we supply the Temptek CGD-5W, a water-cooled portable chiller rated 5.1 tons at 50°F, against the 4.8 tons Drake publishes for this unit at 55°F leaving fluid and 105°F condensing temperature on R407C. Drake's table has no 50°F row for this unit, so its 55°F figure is used; a chiller makes at least as much at a warmer set point, so the pick keeps a margin at 50°F.
Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.