1-805-484-2992

Quotes - Sizing - Sales

PWCT50S

Drake
Product Type Capacity Refrigerant
Packaged Chiller Water-Cooled Packaged 5 Tons @ 55°F R407C or R404A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PWCT50S as shown on this page.

Replacement chiller for the Drake PWCT50S

Description

The Drake PWCT50S is a 5 hp single-circuit scroll packaged water-cooled chiller with a tank, from the PWC / PWCT Scroll line. Drake publishes a capacity table for it rather than a single rating: 5 tons at 55°F leaving fluid and 105°F condensing temperature on R407C, at an EER of 13.1. The same column runs from 3.8 tons at 40°F to 6.5 tons at 70°F. It is offered on R407C for a 25°F to 55°F suction range and R404A for a -10°F to 45°F suction range. Drake lists one ZB42KCE compressor of 5 hp. Its tank holds 60 gallons. Replacement: we supply the Temptek CGD-5W, a water-cooled portable chiller rated 5.1 tons at 50°F, against the 5 tons Drake publishes for this unit at 55°F leaving fluid and 105°F condensing temperature on R407C. Drake's table has no 50°F row for this unit, so its 55°F figure is used; a chiller makes at least as much at a warmer set point, so the pick keeps a margin at 50°F.

Product Overview

Part Number:
PWCT50S
Manufacturer:
Drake
Replacement Unit:
Temptek CGD-5W

Published Capacity

Cooling Capacity:
5 tons at 55°F leaving fluid
Rating Point Used:
55°F leaving fluid, 105°F condensing temperature, R407C
Capacity at 40°F Leaving Fluid:
3.8 tons
Capacity at 45°F Leaving Fluid:
4.2 tons
Capacity at 65°F Leaving Fluid:
6 tons
Capacity at 70°F Leaving Fluid:
6.5 tons
R404A Low-Temperature Range:
2.1 tons at 5°F to 6.5 tons at 60°F
R407C Suction Range:
25°F to 55°F
R404A Suction Range:
-10°F to 45°F

Configuration & Specifications

Horsepower:
5 HP
Compressor:
Scroll
Compressor Model:
1 x ZB42KCE
Circuits:
Single
Condenser:
Water-Cooled
Tank:
Integral tank
Refrigerant:
R407C or R404A

Pump & Reservoir

  • Tank Capacity: 60 gallons

Electrical

  • Voltage Options: 208-230 V single-phase
  • Frequency: 60 Hz

Connections

Process Connections:
1 in F-NPT

Dimensions & Weight

Dimensions (L x W x H):
58 x 34 x 63 in
Weight:
850 lbs

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales