| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Recirculating Chiller | Remote Condenser | 37.5 Tons @ 50°F | HFO |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n POC-5000-540 as shown on this page.
The Filtrine POC-5000-540 is a 37.5-ton open-loop recirculating air-cooled chiller from the POC line, built around Filtrine's storage-type stainless cooling tank with an immersion coil evaporator. Filtrine's chart lists 450,000 Btu/h, 37.5 tons, at 50°F outlet and 90°F ambient, 330,000 Btu/h at 30°F and 540,000 Btu/h at 68°F, the point its model number is named for. As an open-loop chiller its pump draws from an open tank or sump and returns to it, with the thermostat sensing the make-up liquid. Filtrine offers this size with a remote air- or water-cooled condenser only. Replacement: we supply the Temptek MA-40-RC-CC, an air-cooled chilling module with a remote condenser rated 38 tons at 50°F, against the 37.5 tons Filtrine publishes for this unit at 50°F outlet and 90°F ambient. Filtrine rates at 90°F ambient and Temptek at 95°F, the harder condition, so a Temptek unit that covers the Filtrine figure keeps a margin. The Temptek unit runs a closed loop from its own tank, so an open sump on the old system is piped as the return or replaced.
Specifications sourced from Filtrine's published Process Chillers Specifications chart and per-model spec sheets (filtrine.com), October 2026. Filtrine is a trademark of its owner; referenced here for cross-reference only. Filtrine notes that dimensions and shipping weights vary with options. Confirm against the unit nameplate before ordering.