| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Chilling Module | Remote Condenser | 38 Tons | R-454B |
Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n MA-40-RC-CC as shown on this page.
The Temptek MA-40-RC-CC is a chilling module with a remote air-cooled condenser rated 38 tons at 50°F leaving fluid and 115°F condensing temperature, on 2 refrigeration zones. It runs 2 scroll compressors of 20 HP each on R-454B. As a chilling module it carries no reservoir or pumps; it connects to a separate pump-tank station. It is paired with the KCL-63-KR remote air-cooled condenser (4 fans). At a glycol setpoint the published multipliers apply: about 30.4 tons at 40°F, 22.8 at 30°F and 15.2 at 20°F. Also available: the alternate CC-40APT-RC, the same air-cooled chilling module format and capacity class.