| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Glycol Chiller | Modular Base | 19.2 Tons @ 40°F | R-448A |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n GD-27H-MS as shown on this page.
The G&D Chillers GD-27H-MS is a modular base glycol chiller with an oversized reservoir from G&D's Modular Series. G&D publishes it at 230,000 Btu/h at 40°F leaving glycol (about 19.2 tons), 192,000 at 30°F, 157,000 at 20°F, in a 90°F ambient, on R-448A. It carries two 13.5 HP compressors, a 500-gallon reservoir and a 7.5 HP process pump delivering 230 GPM at 25 PSI. Replacement: we supply the Temptek TTOACS-40S-CG-1P, an outdoor air-cooled packaged chiller rated 38.4 tons at 50°F, about 15.4 tons at 20°F on Temptek's published 0.40 multiplier, against the 13.1 tons G&D publishes for this unit at 20°F (its coldest published rating), so it covers every published setpoint.
Specifications sourced from G&D Chillers' published product pages, spec sheets and brochures (gdchillers.com), September 2026. G&D Chillers, Nano Chill, Micro Chill and Fire & Ice are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.