1-805-484-2992

Quotes - Sizing - Sales

GD-150H-3C

G&D Chillers
Product Type Capacity Refrigerant
Glycol Chiller Outdoor Packaged 90.6 Tons @ 40°F R-454C

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n GD-150H-3C as shown on this page.

Replacement chiller for the G&D GD-150H-3C

Description

The G&D Chillers GD-150H-3C is a packaged glycol chiller on semi-hermetic compressors from G&D's Vertical Air Series. G&D publishes it at 1,087,500 Btu/h at 40°F leaving glycol (about 90.6 tons), 910,400 at 30°F, 747,700 at 20°F, in a 90°F ambient, on R-454C. It carries three 50 HP compressors, a 930-gallon reservoir and a 10 HP process pump delivering 340 GPM at 25 PSI. Replacement: we supply the Temptek TTOACS-190D-MZC-2P, an outdoor air-cooled packaged chiller rated 170.1 tons at 50°F, about 68 tons at 20°F on Temptek's published 0.40 multiplier, against the 62.3 tons G&D publishes for this unit at 20°F (its coldest published rating), so it covers every published setpoint.

Product Overview

Part Number:
GD-150H-3C
Manufacturer:
G&D Chillers
Replacement Unit:
Temptek TTOACS-190D-MZC-2P

Published Capacity

Capacity at 40°F Leaving Fluid:
1,087,500 Btu/h (318.7 kW)
Capacity at 30°F Leaving Fluid:
910,400 Btu/h (266.8 kW)
Capacity at 20°F Leaving Fluid:
747,700 Btu/h (219.1 kW)
Rating Basis:
10°F temperature difference, 90°F ambient, sea level

Configuration & Specifications

Compressor:
50 HP (x3)
Refrigerant:
R-454C
Condenser:
Air-Cooled Vertical Discharge
Evaporator:
Stainless Steel Brazed Plate
Controls:
Microprocessor w/ Comm.
Housing:
Powder Coated Aluminum
Electrical Enclosure:
NEMA 3R
Sound Level:
82 dBA at 10 ft

Pump & Reservoir

  • Reservoir: 930 Gallons
  • Process Pump: 10 HP
  • Chiller Pump: 5 HP
  • Process Flow: 340 GPM at 25 PSI
  • Connection Size: 4"

Electrical

  • Voltage: 460-480V
  • Phase: Three Phase
  • Full Load Amps: 340
  • Minimum Circuit Ampacity: 365
  • Maximum Overcurrent Protection: 450

Dimensions & Weight

Dimensions (W x L x H):
96" x 274" x 120"
Operating Weight:
20,500 lbs
Shipping Weight:
12,500 lbs

Specifications sourced from G&D Chillers' published product pages, spec sheets and brochures (gdchillers.com), September 2026. G&D Chillers, Nano Chill, Micro Chill and Fire & Ice are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.