| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Air-Cooled Scroll Chiller | Air-Cooled | 93 Tons nominal | R-410A |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ASC100X as shown on this page.
The Multistack ASC100X is an ASC air-cooled stand-alone chiller with 4 scroll compressors totalling 93 nominal tons, dual refrigeration circuits on R-410A and a brazed plate evaporator. It has 6 condenser fans moving 74,000 cfm and weighs 6,780 lb operating. At 460 V the catalog lists 172 A minimum circuit ampacity and 225 A maximum overcurrent protection. Replacement: we supply the Temptek TTOACS-150D-MZC-2P, an outdoor air-cooled packaged chiller rated 145.8 tons at 50°F, against the 93 tons Multistack publishes for this unit at its total nominal tons (AHRI 550/590). Temptek rates at 50°F, so the 44°F figure is matched on Temptek's published 40°F capacity multiplier of 0.80, which leaves the pick some margin; we confirm it at your set point.
Specifications sourced from Multistack's published ASC air-cooled stand-alone chiller product catalog (multistack.com), October 2026. Multistack is a trademark of its owner; referenced here for cross-reference only. Capacities are the catalog's total nominal tons. Confirm against the unit nameplate before ordering.