1-805-484-2992

Quotes - Sizing - Sales

ASC105X

Multistack
Product Type Capacity Refrigerant
Air-Cooled Scroll Chiller Air-Cooled 107 Tons nominal R-410A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ASC105X as shown on this page.

Replacement chiller for the Multistack ASC105X

Description

The Multistack ASC105X is an ASC air-cooled stand-alone chiller with 4 scroll compressors totalling 107 nominal tons, dual refrigeration circuits on R-410A and a brazed plate evaporator. It has 8 condenser fans moving 86,000 cfm and weighs 7,990 lb operating. At 460 V the catalog lists 204 A minimum circuit ampacity and 250 A maximum overcurrent protection. Replacement: we supply the Temptek TTOACS-150D-MZC-2P, an outdoor air-cooled packaged chiller rated 145.8 tons at 50°F, against the 107 tons Multistack publishes for this unit at its total nominal tons (AHRI 550/590). Temptek rates at 50°F, so the 44°F figure is matched on Temptek's published 40°F capacity multiplier of 0.80, which leaves the pick some margin; we confirm it at your set point.

Product Overview

Part Number:
ASC105X
Manufacturer:
Multistack
Series:
ASC Series
Replacement Unit:
Temptek TTOACS-150D-MZC-2P

Published Capacity

Total Nominal Capacity:
107 tons
Rating Basis:
AHRI Standard 550/590 (guide specification)
Low Ambient Option:
To -20°F

Configuration & Specifications

Compressors:
4 scroll
Refrigeration Circuits:
Dual
Refrigerant:
R-410A
Evaporator:
Brazed plate
Evaporator Water Volume:
14 gallons
Condenser Fans:
8
Total Airflow:
86,000 cfm
Controller:
Carel c.pCO

Electrical (MCA / MOP)

208 V / 3 ph / 60 Hz:
451/600 A
230 V / 3 ph / 60 Hz:
396/500 A
460 V / 3 ph / 60 Hz:
204/250 A
575 V / 3 ph / 60 Hz:
163/200 A

Connections

Chilled Water Connections:
3 in grooved

Dimensions & Weight

Length (X):
172 in
Width (Y):
79 in
Height (Z):
112 in
Shipping Weight:
7,870 lb
Operating Weight:
7,990 lb

Specifications sourced from Multistack's published ASC air-cooled stand-alone chiller product catalog (multistack.com), October 2026. Multistack is a trademark of its owner; referenced here for cross-reference only. Capacities are the catalog's total nominal tons. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales