1-805-484-2992

Quotes - Sizing - Sales

ASC150X

Multistack
Product Type Capacity Refrigerant
Air-Cooled Scroll Chiller Air-Cooled 140 Tons nominal R-410A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ASC150X as shown on this page.

Replacement chiller for the Multistack ASC150X

Description

The Multistack ASC150X is an ASC air-cooled stand-alone chiller with 6 scroll compressors totalling 140 nominal tons, dual refrigeration circuits on R-410A and a brazed plate evaporator. It has 10 condenser fans moving 108,000 cfm and weighs 10,305 lb operating. At 460 V the catalog lists 258 A minimum circuit ampacity and 300 A maximum overcurrent protection. Replacement: we supply the Temptek TTOACS-210D-MZC-2P, an outdoor air-cooled packaged chiller rated 188 tons at 50°F, against the 140 tons Multistack publishes for this unit at its total nominal tons (AHRI 550/590). Temptek rates at 50°F, so the 44°F figure is matched on Temptek's published 40°F capacity multiplier of 0.80, which leaves the pick some margin; we confirm it at your set point.

Product Overview

Part Number:
ASC150X
Manufacturer:
Multistack
Series:
ASC Series
Replacement Unit:
Temptek TTOACS-210D-MZC-2P

Published Capacity

Total Nominal Capacity:
140 tons
Rating Basis:
AHRI Standard 550/590 (guide specification)
Low Ambient Option:
To -20°F

Configuration & Specifications

Compressors:
6 scroll
Refrigeration Circuits:
Dual
Refrigerant:
R-410A
Evaporator:
Brazed plate
Evaporator Water Volume:
16 gallons
Condenser Fans:
10
Total Airflow:
108,000 cfm
Controller:
Carel c.pCO

Electrical (MCA / MOP)

208 V / 3 ph / 60 Hz:
572/700 A
230 V / 3 ph / 60 Hz:
504/600 A
460 V / 3 ph / 60 Hz:
258/300 A
575 V / 3 ph / 60 Hz:
207/250 A

Connections

Chilled Water Connections:
4 in grooved

Dimensions & Weight

Length (X):
286 in
Width (Y):
79 in
Height (Z):
112 in
Shipping Weight:
10,170 lb
Operating Weight:
10,305 lb

Specifications sourced from Multistack's published ASC air-cooled stand-alone chiller product catalog (multistack.com), October 2026. Multistack is a trademark of its owner; referenced here for cross-reference only. Capacities are the catalog's total nominal tons. Confirm against the unit nameplate before ordering.