ICEP014 (60 Hz)

Parker Hannifin
Product Type Capacity Refrigerant
Process Chiller Air-Cooled 3.37 Tons @ 45°F R407C

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ICEP014 (60 Hz) as shown on this page.

Replacement chiller for the Parker Hannifin ICEP014 (60 Hz)

Description

The Parker ICEP014 in its 60 Hz build is a Hyperchill Plus compact chiller for North American supply, with a 17-gallon non-ferrous tank and pump on board. Parker lists 40,454 Btu/h, about 3.37 tons, at 55/45°F water and 95°F ambient on R407C. It pumps 9 GPM at 67 psi on the standard P30 pump. Replacement: we supply the Temptek CGD-5A, an air-cooled portable chiller rated 4.9 tons at 50°F, against the 3.37 tons Parker Hannifin publishes for this unit at 45°F leaving water and 95°F ambient. Parker rates the 60 Hz Hyperchill Plus at 45°F leaving water and 95°F ambient. Temptek rates at 50°F, so the 45°F figure is matched on Temptek's published 40°F multiplier of 0.80, which leaves the pick some margin. Divided by 0.80, the 3.37 tons call for at least 4.21 tons of Temptek 50°F rating.

Product Overview

Part Number:
ICEP014 (60 Hz)
Manufacturer:
Parker Hannifin
Replacement Unit:
Temptek CGD-5A

Published Capacity

Cooling Capacity:
40,454 Btu/h (3.37 tons)
Rating Point:
55/45°F water, 95°F ambient, 0% glycol, sea level
Operating Limits:
Ambient 41 to 118°F; water outlet 33°F minimum

Configuration & Specifications

Compressor:
1 scroll, 1 circuit
Compressor Absorbed Power:
4.48 kW
Refrigerant:
R407C
Axial Fans:
1
Air Flow:
2,808 scfm
Sound Pressure at 32.8 ft:
50 dB(A)
Protection Index:
IP54

Pump & Reservoir

  • Pump: P30 standard
  • Water Flow: 9 GPM
  • Head Pressure: 67 psi
  • Tank Capacity: 17 gallons

Electrical

  • Power Supply: 460 V / 3 ph / 60 Hz

Connections

Water Connections:
3/4 in (female NPT adapters supplied)

Dimensions & Weight

Width:
30 in
Depth:
32 in
Height:
56 in
Weight (with pallet and charge):
386 lb

Specifications sourced from Parker Hannifin's published Hyperchill bulletins (parker.com), October 2026. Parker, Hiross and Hyperchill are trademarks of their owner; referenced here for cross-reference only. Capacities are Parker's figures at the rating point shown. Confirm against the unit nameplate before ordering.