Replacement unit for the Parker Hannifin Hyperchill Plus 60 Hz Series

Hyperchill Plus 60 Hz Series

The North American build of the Hyperchill Plus: eight 60 Hz sizes, 4,668 to 65,738 Btu/h at 45°F water and 95°F ambient.

PRODUCT TYPE CAPACITY MODELS
Process Chiller Compact, 60 Hz 4,668 to 65,738 Btu/h 8

Specifications


Configuration & Size

Capacity:
4,668 to 65,738 Btu/h
Models:
8 part numbers
Refrigerant:
R407C
Tank:
4 to 26 gallons
Supply:
230 V 1 ph or 460 V 3 ph, 60 Hz

Construction

  • Non-ferrous hydraulic circuit
  • Tank and pump inside
  • Scroll compressor from ICEP007
  • P30 or P50 pump
  • UL approval offered ICEP003 to ICEP024

Ratings

  • 55/45°F water, 95°F ambient
  • Sea level, 0% glycol
  • Ambient 41 to 118°F
  • Water outlet 33°F minimum

Specifications sourced from Parker Hannifin's published Hyperchill bulletins (parker.com), October 2026. Parker, Hiross and Hyperchill are trademarks of their owner; referenced here for cross-reference only. Capacities are Parker's figures at the rating point shown. Confirm against the unit nameplate before ordering.

Hyperchill Plus 60 Hz, 0.4 to 5.5 Tons

Rated the American Way

Eight models. From the ICEP002 at 4,668 Btu/h to the ICEP024 at 65,738 Btu/h, at 55/45°F water and 95°F ambient at sea level.

North American power. 230 V single-phase on the ICEP002 to ICEP005 and 460 V three-phase from the ICEP007; UL approval is offered on the ICEP003 to ICEP024.

Two pumps. The standard P30 delivers 44 to 67 psi at nominal flow; the P50 option, from the ICEP003, 78 to 88 psi.

Its own correction table. Parker lists a factor of 1.15 at 59°F water and 0.9 at 41°F, and 0.95 at 104°F ambient.



engineering drawings spread on a desk

One compressor, a non-ferrous tank and a pump in a 30-inch wide cabinet for 60 Hz supply.

Request a Quote

Hyperchill Plus 60 Hz Series Applications

Lasers
Lasers
Machine tools
Machine tools
Medical imaging
Medical imaging
Small loops
Small loops

schematic of the Hyperchill Plus 60 Hz series circuit, showing where the process fluid and the condenser heat go

45°F Is Colder Than Temptek's 50°F

Parker rates this build at 45°F leaving water. Temptek rates at 50°F, where a chiller makes more, so a straight tons-to-tons match would come up short. The pick is sized on Temptek's published 40°F multiplier of 0.80, which covers the 45°F figure.

Every part-number page below names the Temptek unit we supply in its place, sized from Parker's 45°F figure on Temptek's 0.80 multiplier at 40°F.
Call and talk it through with an engineer: 1-805-484-2992

Hyperchill Plus at 60 Hz: Questions We Get

Closely: the listed P30 flow gives a rise of about 9°F on both the ICEP010 and the ICEP024. The ICEP010 makes 2.5 tons, 30,000 Btu/h, and its P30 pump moves 6.6 GPM at 51 psi: 30,000 divided by 500 x 6.6 is about 9.1°F. For the ICEP024, 65,738 Btu/h on 14.6 GPM at 44 psi works out to about 9.0°F. So a Hyperchill Plus loop is designed around a fairly wide rise and modest flow. A laser that needs a narrow rise wants more flow, and the higher-head P50 may be what the existing unit carries. Tell us which pump is fitted.

At least about 6.85 tons. The ICEP024 is rated 65,738 Btu/h, about 5.48 tons, at 45°F leaving water, and dividing by Temptek's 40°F multiplier of 0.80 brings it onto the 50°F basis Temptek publishes. The same step turns the ICEP010's 2.5 tons into 3.12 tons, which is why we supply the 4-ton CG-4A for it. The mistake is matching 5.48 tons to a unit rated about 5.5 tons at 50°F; it would come up short every time the loop ran at 45°F. Using the 40°F multiplier on a 45°F duty is deliberately on the safe side.

About 2.14 tons, against its 2.5-ton catalog figure. Parker's correction table gives 0.9 at 41°F water and 0.95 at 104°F ambient, and multiplying the two gives 0.855. The same unit at 59°F water, with the 1.15 factor, makes about 2.88 tons. That spread, from 2.14 to 2.88 tons for one model, is why the rating point has to be named before any comparison. A plant that bought on the catalog figure and later lowered the set point will see the shortfall as a slowly climbing loop temperature on hot days. The ratings also assume sea level and 0% glycol, so mention both in the request if your site differs.

It means the unit can be set close to freezing, but Parker's ratings assume 0% glycol, so a loop near 33°F has no published capacity and almost certainly carries glycol. Temptek's 0.80 multiplier covers 40°F leaving fluid; colder than that, send the set point and the glycol percentage and call for rating at that condition, rather than scaling from the 45°F line.