| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Process Chiller | Air-Cooled | 4.7 Tons @ 45°F | R407C |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ICEP020 (60 Hz) as shown on this page.
The Parker ICEP020 in its 60 Hz build is a Hyperchill Plus compact chiller for North American supply, with a 26-gallon non-ferrous tank and pump on board. Parker lists 56,403 Btu/h, about 4.7 tons, at 55/45°F water and 95°F ambient on R407C. It pumps 12.5 GPM at 61 psi on the standard P30 pump. Replacement: we supply the Temptek CGD-7.5A, an air-cooled portable chiller rated 7.2 tons at 50°F, against the 4.7 tons Parker Hannifin publishes for this unit at 45°F leaving water and 95°F ambient. Parker rates the 60 Hz Hyperchill Plus at 45°F leaving water and 95°F ambient. Temptek rates at 50°F, so the 45°F figure is matched on Temptek's published 40°F multiplier of 0.80, which leaves the pick some margin. Divided by 0.80, the 4.7 tons call for at least 5.88 tons of Temptek 50°F rating.
Specifications sourced from Parker Hannifin's published Hyperchill bulletins (parker.com), October 2026. Parker, Hiross and Hyperchill are trademarks of their owner; referenced here for cross-reference only. Capacities are Parker's figures at the rating point shown. Confirm against the unit nameplate before ordering.