| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Process Chiller | Air-Cooled | 7.56 Tons nominal | R513A |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ICEP027E as shown on this page.
The Parker ICEP027E is a Hyperchill Plus-E compact chiller on R513A, a low-GWP refrigerant in the non-flammable A1 class, with a 100-liter tank and a 3 bar pump. Parker lists 26.6 kW, about 7.56 tons, at 20/15°C water and 25°C ambient, with an EER of 4.64. Replacement: we supply the Temptek CGD-10A, an air-cooled portable chiller rated 9.8 tons at 50°F, against the 7.56 tons Parker Hannifin publishes for this unit at its nominal point of 15°C water and 25°C ambient. Parker rates the Plus-E at 15°C (59°F) water and 25°C (77°F) ambient and its bulletin gives no correction factors, so the pick covers the full nominal figure. Temptek's rating point is colder and hotter, which leaves the pick margin; we confirm it at your set point. The Temptek unit is built for North American 460 V / 60 Hz or 230 V supply, not 50 Hz.
Specifications sourced from Parker Hannifin's published Hyperchill bulletins (parker.com), October 2026. Parker, Hiross and Hyperchill are trademarks of their owner; referenced here for cross-reference only. Capacities are Parker's figures at the rating point shown. Confirm against the unit nameplate before ordering.