1-805-484-2992

Quotes - Sizing - Sales

ICEP034E

Parker Hannifin
Product Type Capacity Refrigerant
Process Chiller Air-Cooled 9.41 Tons nominal R513A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ICEP034E as shown on this page.

Replacement chiller for the Parker Hannifin ICEP034E

Description

The Parker ICEP034E is a Hyperchill Plus-E compact chiller on R513A, a low-GWP refrigerant in the non-flammable A1 class, with a 200-liter tank and a 3 bar pump. Parker lists 33.1 kW, about 9.41 tons, at 20/15°C water and 25°C ambient, with an EER of 4.95. Replacement: we supply the Temptek CGD-10A, an air-cooled portable chiller rated 9.8 tons at 50°F, against the 9.41 tons Parker Hannifin publishes for this unit at its nominal point of 15°C water and 25°C ambient. Parker rates the Plus-E at 15°C (59°F) water and 25°C (77°F) ambient and its bulletin gives no correction factors, so the pick covers the full nominal figure. Temptek's rating point is colder and hotter, which leaves the pick margin; we confirm it at your set point. The Temptek unit is built for North American 460 V / 60 Hz or 230 V supply, not 50 Hz.

Product Overview

Part Number:
ICEP034E
Manufacturer:
Parker Hannifin
Replacement Unit:
Temptek CGD-10A

Published Capacity

Nominal Cooling Capacity:
33.1 kW (9.41 tons)
Rating Point:
20/15°C water, 25°C ambient, 0% glycol
Correction Factors:
Not published in the Plus-E bulletin
Max Ambient:
48°C

Configuration & Specifications

Compressor Type:
Hermetic scroll
Total Absorbed Power:
6.7 kW
EER:
4.95
SEPR HT:
5.60
Refrigerant:
R513A (A1, non-flammable)
Air Flow:
17,337 m³/h
Sound Pressure at 10 m:
53 dB(A)
Protection Index:
IP54

Pump & Reservoir

  • Pump: P30, 3 bar standard
  • Pump Max Power: 2.2 kW
  • Water Flow (nominal / max): 5.7/18 m³/h
  • Tank Capacity: 200 liters (53 gallons)

Electrical

  • Power Supply: 400 V / 3 ph / 50 Hz

Connections

Water Connections:
1-1/2 in

Dimensions & Weight

Width:
856 mm
Depth:
1956 mm
Height:
1680 mm
Weight (with charge and pallet):
485 kg

Specifications sourced from Parker Hannifin's published Hyperchill bulletins (parker.com), October 2026. Parker, Hiross and Hyperchill are trademarks of their owner; referenced here for cross-reference only. Capacities are Parker's figures at the rating point shown. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales