1-805-484-2992

Quotes - Sizing - Sales
Replacement unit for the Parker Hannifin Hyperchill Plus-E Series

Hyperchill Plus-E Series

Parker's low-GWP compact chiller: the Hyperchill Plus-E on non-flammable R513A, 2.9 to 120.6 kW nominal.

PRODUCT TYPE CAPACITY MODELS
Process Chiller Compact, R513A 2.9 to 120.6 kW 14

Specifications


Configuration & Size

Capacity:
2.9 to 120.6 kW nominal
Models:
14 part numbers
Refrigerant:
R513A
Tank:
15 to 400 liters
Supply:
230 V 1 ph or 400 V 3 ph, 50 Hz

Construction

  • R513A, safety class A1
  • Non-ferrous hydraulic circuit
  • Tank and 3 bar pump inside
  • MODBUS RTU on every model
  • IP54 from ICEP008E

Ratings

  • 20/15°C water, 25°C ambient
  • EER 2.38 to 4.95
  • Max ambient 48°C
  • No correction factors published

Specifications sourced from Parker Hannifin's published Hyperchill bulletins (parker.com), October 2026. Parker, Hiross and Hyperchill are trademarks of their owner; referenced here for cross-reference only. Capacities are Parker's figures at the rating point shown. Confirm against the unit nameplate before ordering.

Hyperchill Plus-E, 2.9 to 120.6 kW

Low-GWP Without the Flammability

Fourteen models. From the ICEP003E at 2.9 kW to the ICEP120E at 120.6 kW, at 20/15°C water and 25°C ambient.

R513A. A low-GWP refrigerant in the non-flammable A1 class, so the chiller installs indoors or outdoors without a flammability assessment.

Efficiency is published. EER from 2.38 on the smallest piston unit to 4.95 on the ICEP034E, and SEPR HT of 5.00 to 5.60.

Tanks from 15 to 400 liters. In cabinets from 755 mm wide to the 1,050 x 2,500 mm frame of the ICEP080E to ICEP120E.



wooden crates on a shipping dock

Piston or scroll compressors on R513A, a non-ferrous tank and a 3 bar pump in one cabinet.

Request a Quote

Hyperchill Plus-E Series Applications

Low-GWP duty
Low-GWP duty
Lasers
Lasers
Plastics molding
Plastics molding
Chemical process
Chemical process

schematic of the Hyperchill Plus-E series circuit, showing where the process fluid and the condenser heat go

No Correction Table for the Plus-E

The Plus-E bulletin gives the nominal figure at 15°C water and 25°C ambient but no correction factors. We do not borrow another range's factors: the pick covers the full nominal figure, which leaves margin at Temptek's colder and hotter rating point. The glycol type and mix guide covers the fluid side.

Every part-number page below names the Temptek unit we supply in it's place, sized to cover Parker's full nominal figure, because the Plus-E bulletin publishes no correction factors.
Call and talk it through with an engineer: 1-805-484-2992

Plus-E on R513A: What Carries Over

About 39.8 kW: the 33.1 kW it removes from the water plus the 6.7 kW of total absorbed power Parker lists. The ratio, about 4.94, is the published 4.95 EER. Indoors that heat stays in the room and can lift it enough to trim the unit's own capacity, so tell us whether the Temptek unit goes indoors or on a pad.

Yes: the CGD-10A clears Parker's nominal ICEP034E figure by about 4 percent even at Temptek's harder rating point, and the TTI-40A clears the ICEP120E's 34.29 tons by about 17 percent. Parker's figure is at 15°C water and 25°C ambient, while Temptek's is colder on the water side and hotter on the air side, so at Parker's condition the Temptek unit makes more than its rating and the true margin is wider than 4 percent. With no Plus-E correction table, that extra cannot be put into a number; give us your set point and room temperature, and we rate it there.

The power supply comes first. The Plus-E is built for 230 V single-phase or 400 V three-phase at 50 Hz, while Temptek's are 60 Hz builds, for 460 V or 230 V, so the site's supply has to be settled before anything else. Two other items need naming in the request. MODBUS RTU comes on every Plus-E, so if a building system polls the chiller, list the points it reads. And the cabinets run from 755 mm wide up to a frame 1,050 mm by 2,500 mm on the ICEP080E to ICEP120E; a Temptek unit of the same capacity is a different package, so measure the space and the door it has to pass through.