| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Process Chiller | Air-Cooled | 1.48 Tons nominal | R407C |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ICEP005-W as shown on this page.
The Parker ICEP005-W is a Hyperchill Plus compact chiller with a non-ferrous hydraulic circuit, a 22.5-liter tank and a 3 bar pump. Parker lists 5.2 kW, about 1.48 tons, at 20/15°C water and 25°C ambient on R407C. By Parker's correction factors that is about 1.14 tons at 10°C water and 35°C ambient. Replacement: we supply the Temptek CF-1.5A, a fractional-ton portable chiller rated 1.5 tons at 50°F, against the 1.14 tons Parker Hannifin publishes for this unit at 10°C (50°F) water and 35°C (95°F) ambient. Parker rates the Hyperchill Plus at 15°C water and 25°C ambient and publishes correction factors of 0.87 for 10°C water and 0.89 for 35°C ambient; the figure compared is the nominal capacity times both, which is Temptek's rating point. Parker calls the factors approximate, so we confirm the pick at your set point. The Temptek unit is built for North American 460 V / 60 Hz or 230 V supply, not 50 Hz.
Specifications sourced from Parker Hannifin's published Hyperchill bulletins (parker.com), October 2026. Parker, Hiross and Hyperchill are trademarks of their owner; referenced here for cross-reference only. Capacities are Parker's figures at the rating point shown. Confirm against the unit nameplate before ordering.