1-805-484-2992

Quotes - Sizing - Sales
Replacement unit for the Parker Hannifin Hyperchill Plus Series

Hyperchill Plus Series

Parker's compact chiller: the Hyperchill Plus, 1.7 to 58.3 kW nominal, with a non-ferrous water circuit and a tank and pump inside.

PRODUCT TYPE CAPACITY MODELS
Process Chiller Compact, Non-Ferrous 1.7 to 58.3 kW 12

Specifications


Configuration & Size

Capacity:
1.7 to 58.3 kW nominal
Models:
12 part numbers
Refrigerant:
R407C
Tank:
15 to 250 liters
Supply:
230 V 1 ph or 400 V 3 ph, 50 Hz

Construction

  • Non-ferrous hydraulic circuit
  • Stainless plate evaporator
  • Tank and 3 bar pump inside
  • Scroll compressor from ICEP007
  • IP54 from ICEP007

Ratings

  • 20/15°C water, 25°C ambient
  • Factor 0.87 at 10°C water
  • Factor 0.89 at 35°C ambient
  • Ambient 5 to 48°C

Specifications sourced from Parker Hannifin's published Hyperchill bulletins (parker.com), October 2026. Parker, Hiross and Hyperchill are trademarks of their owner; referenced here for cross-reference only. Capacities are Parker's figures at the rating point shown. Confirm against the unit nameplate before ordering.

Hyperchill Plus, 1.7 to 58.3 kW

A Non-Ferrous Water Circuit

Twelve models. From the ICEP002 at 1.7 kW to the ICEP060 at 58.3 kW, at 20/15°C water and 25°C ambient.

Clean water. A non-ferrous tank (stainless steel from ICEP005), a stainless plate evaporator and a non-ferrous pump keep the coolant from corroding.

Piston, then scroll. Hermetic piston compressors on the ICEP002 to ICEP005 at 230 V single-phase; scroll compressors and 400 V three-phase from the ICEP007.

Hot rooms. Standard units run to 48°C ambient, and a tropicalized option to 53°C.



shelves of spare parts in a warehouse

One compressor, a stainless plate evaporator, a non-ferrous tank and a 3 bar pump in one cabinet.

Request a Quote

Hyperchill Plus Series Applications

Lasers
Lasers
Machine tools
Machine tools
Plastics molding
Plastics molding
Medical imaging
Medical imaging

schematic of the Hyperchill Plus series circuit, showing where the process fluid and the condenser heat go

Correcting to 50°F and 95°F

Parker rates the Hyperchill Plus at 15°C water and 25°C ambient and prints factors of 0.87 for 10°C water and 0.89 for 35°C ambient. Multiply the two and the nominal figure falls to about 77 percent: an ICEP024 listed at 23.6 kW makes about 18.3 kW, 5.2 tons. The glycol chiller sizing guide works a load from flow and temperature rise.

Every part-number page below names the Temptek unit we supply in its place, sized from Parker's nominal figure corrected to 10°C water and 35°C ambient with Parker's own published factors.
Call and talk it through with an engineer: 1-805-484-2992

Hyperchill Plus: Circuit Materials, Power and Sizing

What the piping is made of. The Hyperchill Plus keeps its water circuit non-ferrous, so loops built around it are often copper, stainless or plastic and have run clean for years. If mild-steel pipe has been added since, rust particles reach the evaporator and the coolant clouds, and lasers and imaging systems are the first to complain. Tell us the pipe materials, any filter in the loop and the coolant in use, and we confirm the Temptek unit's wetted materials against them before the order.

Because the comparison is made at 10°C water and 35°C ambient, where the ICEP014 corrects to 3.21 tons, leaving the 4-ton CG-4A about 25 percent of headroom. Uncorrected, the ICEP014's figure at Parker's nominal point works out to about 4.15 tons, so a straight nominal comparison makes the CG-4A look too small. Once Parker's own water and ambient factors are applied, it is not. The same correction is applied on every part-number page in this range, so compare corrected figures only.

About 45.1 kW, roughly 12.8 tons, from its 58.3 kW nominal figure. Parker's water and ambient factors, 0.87 and 0.89, multiply to about 0.774, and 58.3 x 0.774 is 45.1. The ton figure uses the same conversion this page uses for the ICEP024, 23.6 kW to 6.7 tons. On the largest model the correction removes about 13 kW, so skipping it is not a rounding error. The ICEP060 is a 400 V three-phase, 50 Hz scroll machine, and Temptek units are North American 60 Hz builds, so name the supply with the request.

On a rating at the actual room temperture, because the only ambient factor quoted for the range is 0.89 at 35°C. The range runs to 48°C on standard units and 53°C on the tropicalized option, but no factor is quoted here for those temperatures, and we do not extrapolate one. A unit sitting beside a molding press or in a hot mezzanine may see well above 35°C in summer, and its capacity there is lower than any corrected figure on the part-number page. Measure condenser inlet air on a hot afternoon and send it with the request; the Temptek unit is then rated at that condition, or the plan moves the condenser heat somewhere cooler.

Only where the unit sits in spray, washdown or heavy dust. The ICEP002 and ICEP005 cabinets are IP33, against IP54 from the ICEP007, so the smallest units are generaly better suited to a lab bench or clean room than to a wet machine shop. If a small unit has lived next to coolant mist and shows corroded electrics, the replacement needs a drier location or more protection. Describe where it sits, and send a photo if the cabinet shows wear.

Quote Request Form:

Questions?

1-805-484-2992