| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Glycol Chiller | Air-Cooled Packaged | 6.72 Tons @ 35°F | R448 / R449 |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n M5M108F2R4100-A-V as shown on this page.
The PRO M5M108F2R4100-A-V is a 9 hp low-temperature glycol chiller from PRO's legacy M5 line, for chilled fluid down to -5°F, indoors or outdoors. PRO publishes capacity at 90°F air: 27,400 Btu/h at -5°F, 38,000 Btu/h at 5°F, 50,600 Btu/h at 15°F, 63,900 Btu/h at 25°F, 80,600 Btu/h at 35°F, 101,700 Btu/h at 45°F leaving fluid. It carries a 100-gallon tank and a pump rated 40 GPM at 151 ft of head, on R448/R449. Replacement: we supply the Temptek TTOACS-15S-CG-1P, an outdoor air-cooled packaged chiller rated 14.4 tons at 50°F, against the 6.72 tons PRO Refrigeration publishes for this unit at 35°F leaving glycol and 90°F ambient. PRO publishes no 50°F or usable 30°F figure here, so its 35°F figure is matched on Temptek's 30°F multiplier of 0.60; Temptek makes more than that at 35°F, so the pick keeps a margin. We confirm it at your set point. Divided by 0.60, the 6.72 tons call for at least 11.2 tons of Temptek 50°F rating.
Specifications sourced from PRO Refrigeration's published chiller data sheets, series one-sheets and legacy specification tables (prochiller.com), October 2026. PRO Refrigeration, PRO Chiller Systems, Chill&Flow, ChilStar, PRO4, V Piston, V-Scroll, Revolution, PROGreen and PROElliot are trademarks of their owner; referenced here for cross-reference only. PRO publishes these as estimated capacities. Confirm against the unit nameplate before ordering.