1-805-484-2992

Quotes - Sizing - Sales

M5M107F2R420-A-V

PRO Refrigeration
Product Type Capacity Refrigerant
Glycol Chiller Air-Cooled Packaged 5.13 Tons @ 35°F R448 / R449

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n M5M107F2R420-A-V as shown on this page.

Replacement chiller for the PRO Refrigeration M5M107F2R420-A-V

Description

The PRO M5M107F2R420-A-V is a 7 hp low-temperature glycol chiller from PRO's legacy M5 line, for chilled fluid down to -5°F, indoors or outdoors. PRO publishes capacity at 90°F air: 22,600 Btu/h at -5°F, 29,900 Btu/h at 5°F, 38,300 Btu/h at 15°F, 50,120 Btu/h at 25°F, 61,560 Btu/h at 35°F, 69,500 Btu/h at 45°F leaving fluid. It carries a 20-gallon tank and a pump rated 30 GPM at 114 ft of head, on R448/R449. Replacement: we supply the Temptek TTOACS-10S-CG-1P, an outdoor air-cooled packaged chiller rated 10.2 tons at 50°F, against the 5.13 tons PRO Refrigeration publishes for this unit at 35°F leaving glycol and 90°F ambient. PRO publishes no 50°F or usable 30°F figure here, so its 35°F figure is matched on Temptek's 30°F multiplier of 0.60; Temptek makes more than that at 35°F, so the pick keeps a margin. We confirm it at your set point. Divided by 0.60, the 5.13 tons call for at least 8.55 tons of Temptek 50°F rating.

Product Overview

Part Number:
M5M107F2R420-A-V
Manufacturer:
PRO Refrigeration
Series:
M5 Series
Replacement Unit:
Temptek TTOACS-10S-CG-1P

Published Capacity

Capacity at -5°F, 90°F Air:
22,600 Btu/h (1.88 tons)
Capacity at 5°F, 90°F Air:
29,900 Btu/h (2.49 tons)
Capacity at 15°F, 90°F Air:
38,300 Btu/h (3.19 tons)
Capacity at 25°F, 90°F Air:
50,120 Btu/h (4.18 tons)
Capacity at 35°F, 90°F Air:
61,560 Btu/h (5.13 tons)
Capacity at 45°F, 90°F Air:
69,500 Btu/h (5.79 tons)
Temperature Range:
-5 to 45°F

Configuration & Specifications

Horsepower:
7 HP
Refrigerant:
R448 / R449
Condenser Air Flow:
3,400 CFM
Sound Level:
84 dB

Pump & Reservoir

  • Pump: 30 GPM at 114 ft TDH
  • Tank: 20 gallons

Electrical

  • MCA / MOP at 208-230/3: 44/71 A
  • MCA / MOP at 460/3: 25/40 A

Connections

Fluid Connections:
2 in MNPT

Dimensions & Weight

Dimensions (L x W x H):
72 x 46 x 78 in
Shipping Weight:
1,400 lbs
Operating Weight:
2,300 lbs

Specifications sourced from PRO Refrigeration's published chiller data sheets, series one-sheets and legacy specification tables (prochiller.com), October 2026. PRO Refrigeration, PRO Chiller Systems, Chill&Flow, ChilStar, PRO4, V Piston, V-Scroll, Revolution, PROGreen and PROElliot are trademarks of their owner; referenced here for cross-reference only. PRO publishes these as estimated capacities. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992