| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Chilling Module | Remote Condenser | 36 Tons | R-410A |
Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n MA-35-RC-C as shown on this page.
The Temptek MA-35-RC-C is a chilling module with a remote air-cooled condenser rated 36 tons at 50°F leaving fluid and 115°F condensing temperature, on 1 refrigeration zone. It runs a 35 HP discus compressor on R-410A. As a chilling module it carries no reservoir or pumps; it connects to a separate pump-tank station. At a glycol setpoint the published multipliers apply: about 28.8 tons at 40°F, 21.6 at 30°F and 14.4 at 20°F. Also available: the alternate C-40APT-RC, the next size up in the same format.