| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Chilling Module | Remote Condenser | 36.7 Tons | R-454B |
Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n MA-40-RC-C as shown on this page.
The Temptek MA-40-RC-C is a chilling module with a remote air-cooled condenser rated 36.7 tons at 50°F leaving fluid and 115°F condensing temperature, on 1 refrigeration zone. It runs a 40 HP scroll compressor on R-454B. As a chilling module it carries no reservoir or pumps; it connects to a separate pump-tank station. It is paired with the KCL-56-KR remote air-cooled condenser (3 fans). At a glycol setpoint the published multipliers apply: about 29.36 tons at 40°F, 22.02 at 30°F and 14.68 at 20°F. Also available: the alternate C-40APT-RC, the same air-cooled chilling module format and capacity class.