1-805-484-2992

Quotes - Sizing - Sales

MW-35-C

Temptek
Product Type Capacity Refrigerant
Chilling Module Water-Cooled 35 Tons R-407C

Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n MW-35-C as shown on this page.

Chiller equivalent to Temptek MW-35-C

Description

The Temptek MW-35-C is a water-cooled chilling module rated 35 tons at 50°F leaving fluid and 115°F condensing temperature, on 1 refrigeration zone. It runs a 35 HP discus compressor on R-407C. As a chilling module it carries no reservoir or pumps; it connects to a separate pump-tank station. At a glycol setpoint the published multipliers apply: about 28 tons at 40°F, 21 at 30°F and 14 at 20°F. Also available: the alternate C-40WPT, the next size up in the same format.

Product Overview

Part Number:
MW-35-C
Manufacturer:
Temptek
Alternate Unit:
C-40WPT

Configuration & Specifications

Refrigeration Zones Quantity:
1
Compressor Quantity:
1
Compressor HP:
35
Compressor Type:
Discus
Total Capacity:
35
Refrigerant Type:
R-407C
Condenser City Water:
33.5 GPM
Condenser Tower Water:
105 GPM
Rating Basis:
50°F leaving fluid, 115°F condensing

Electrical

Voltage:
230V / 460V / 575V
Phase:
Three Phase
Frequency:
60 Hz
Full Load Amps:
108.0 (230V) / 54.0 (460V) / 43.0 (575V)

Connections, Dimensions & Weight

To Process Connection:
2-1/2"
From Process Connection:
2-1/2"
Height:
57"
Width:
29"
Depth:
70"
Shipping Weight:
1,150 lbs

Quote Request Form:

Questions?

1-805-484-2992