1-805-484-2992

Quotes - Sizing - Sales

MW-40-C

Temptek
Product Type Capacity Refrigerant
Chilling Module Water-Cooled 36.7 Tons R-454B

Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n MW-40-C as shown on this page.

Chiller equivalent to Temptek MW-40-C

Description

The Temptek MW-40-C is a water-cooled chilling module rated 36.7 tons at 50°F leaving fluid and 115°F condensing temperature, on 1 refrigeration zone. It runs a 40 HP scroll compressor on R-454B. As a chilling module it carries no reservoir or pumps; it connects to a separate pump-tank station. At a glycol setpoint the published multipliers apply: about 29.36 tons at 40°F, 22.02 at 30°F and 14.68 at 20°F. Also available: the alternate C-40WPT, the same water-cooled chilling module format and capacity class.

Product Overview

Part Number:
MW-40-C
Manufacturer:
Temptek
Alternate Unit:
C-40WPT

Configuration & Specifications

Refrigeration Zones Quantity:
1
Compressor Quantity:
1
Compressor HP:
40
Compressor Type:
Scroll
Total Capacity:
36.7
Refrigerant Type:
R-454B
Rating Basis:
50°F leaving fluid, 115°F condensing

Electrical

Voltage:
230V / 460V / 575V
Phase:
Three Phase
Frequency:
60 Hz
Full Load Amps:
164.0 (230V) / 82.0 (460V) / 66.0 (575V)

Connections, Dimensions & Weight

To Process Connection:
2-1/2"
From Process Connection:
2-1/2"
Height:
57"
Width:
36"
Depth:
84"
Shipping Weight:
1,200 lbs

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales