Description
The Temptek TTI-150W is a water-cooled central chiller rated 150 tons at 50°F leaving fluid and 115°F condensing temperature, on 3 refrigeration zones. It runs 6 scroll compressors of 25 HP each on R-454B. The process pump delivers 420 GPM at 55 PSI (20 HP) from a 1,200 gallons reservoir. Condenser water is listed at 224 GPM of 60°F city water or 448 GPM of 85°F tower water. Also available: the alternate TI-150W, the same water-cooled central format and capacity class.
Product Overview
Part Number:
TTI-150W
Manufacturer:
Temptek
Configuration & Specifications
Refrigeration Zones Quantity:
3
Compressor Quantity:
6
Compressor Horsepower:
25
Compressor Type:
Scroll
Total Capacity:
150 tons
Refrigerant Type:
R-454B
Condenser City Water:
224 GPM
Condenser Tower Water:
448 GPM
Rating Basis:
50°F leaving fluid, 115°F condensing
Process Pump & Reservoir
- Process Pump HP: 20
- Process Pump GPM: 420
- Process Pump PSI: 55
- Evaporator Pump HP: 10
- Evaporator Pump GPM: 359
- Reservoir Operating: 1,200 gallons
- Reservoir Holding: 1,475 gallons
Electrical
- Voltage: 230V / 460V / 575V
- Phase: Three Phase
- Frequency: 60 Hz
- Full Load Amps: 686.0 (230V) / 343.0 (460V) / 275.0 (575V)
Connections, Dimensions & Weight
To Process Connection:
6"
From Process Connection:
6"
Water Make-Up Connection:
1-1/2"
Overflow Connection:
6"
Condenser Connection:
6"
Height:
114"
Width:
147"
Depth:
147"
Shipping Weight:
9,600 lbs
Operating Weight:
23,820 lbs