Description
The Temptek TTI-180WD is a water-cooled central chiller rated 178 tons at 50°F leaving fluid and 115°F condensing temperature, on 2 refrigeration zones. It runs 2 screw compressors of 90 HP each on R-513A. The process pump delivers 432 GPM at 55 PSI (20 HP) from a 1,200 gallons reservoir. Condenser water is listed at 267 GPM of 60°F city water or 534 GPM of 85°F tower water. Also available: the alternate TI-180WD, the same water-cooled central format and capacity class.
Product Overview
Part Number:
TTI-180WD
Manufacturer:
Temptek
Configuration & Specifications
Refrigeration Zones Quantity:
2
Compressor Quantity:
2
Compressor Horsepower:
90
Compressor Type:
Screw
Total Capacity:
178 tons
Refrigerant Type:
R-513A
Condenser City Water:
267 GPM
Condenser Tower Water:
534 GPM
Rating Basis:
50°F leaving fluid, 115°F condensing
Process Pump & Reservoir
- Process Pump HP: 20
- Process Pump GPM: 432
- Process Pump PSI: 55
- Evaporator Pump HP: 10
- Evaporator Pump GPM: 432
- Reservoir Operating: 1,200 gallons
- Reservoir Holding: 1,475 gallons
Electrical
- Voltage: 230V / 460V / 575V
- Phase: Three Phase
- Frequency: 60 Hz
- Full Load Amps: 758.0 (230V) / 379.0 (460V) / 304.0 (575V)
Connections, Dimensions & Weight
To Process Connection:
6"
From Process Connection:
6"
Water Make-Up Connection:
1-1/2"
Overflow Connection:
4"
Condenser Connection:
4"
Height:
114"
Width:
147"
Depth:
147"
Shipping Weight:
7,500 lbs
Operating Weight:
21,000 lbs