Description
The Temptek TTI-180W is a water-cooled central chiller rated 180 tons at 50°F leaving fluid and 115°F condensing temperature, on 3 refrigeration zones. It runs 6 scroll compressors of 30 HP each on R-410A. The process pump delivers 540 GPM at 55 PSI (25 HP) from a 1,200 gallons reservoir. Condenser water is listed at 259 GPM of 60°F city water or 518 GPM of 85°F tower water. Also available: the alternate TI-180W, the same water-cooled central format and capacity class.
Product Overview
Part Number:
TTI-180W
Manufacturer:
Temptek
Configuration & Specifications
Refrigeration Zones Quantity:
3
Compressor Quantity:
6
Compressor Horsepower:
30
Compressor Type:
Scroll
Total Capacity:
180 tons
Refrigerant Type:
R-410A
Condenser City Water:
259 GPM
Condenser Tower Water:
518 GPM
Rating Basis:
50°F leaving fluid, 115°F condensing
Process Pump & Reservoir
- Process Pump HP: 25
- Process Pump GPM: 540
- Process Pump PSI: 55
- Evaporator Pump HP: 15
- Evaporator Pump GPM: 415
- Reservoir Operating: 1,200 gallons
- Reservoir Holding: 1,475 gallons
Electrical
- Voltage: 230V / 460V / 575V
- Phase: Three Phase
- Frequency: 60 Hz
- Full Load Amps: 884.0 (230V) / 442.0 (460V) / 354.0 (575V)
Connections, Dimensions & Weight
To Process Connection:
6"
From Process Connection:
6"
Water Make-Up Connection:
1-1/2"
Overflow Connection:
6"
Condenser Connection:
6"
Height:
114"
Width:
147"
Depth:
147"
Shipping Weight:
10,500 lbs
Operating Weight:
23,700 lbs