Description
The Temptek TTI-80W is a water-cooled central chiller rated 85.2 tons at 50°F leaving fluid and 115°F condensing temperature, on 2 refrigeration zones. It runs 2 scroll compressors of 40 HP each on R-454B. The process pump delivers 240 GPM at 70 PSI (15 HP) from a 1,200 gallons reservoir. Condenser water is listed at 128 GPM of 60°F city water or 258 GPM of 85°F tower water. Also available: the alternate TI-80W, the same water-cooled central format and capacity class.
Product Overview
Part Number:
TTI-80W
Manufacturer:
Temptek
Configuration & Specifications
Refrigeration Zones Quantity:
2
Compressor Quantity:
2
Compressor Horsepower:
40
Compressor Type:
Scroll
Total Capacity:
85.2 tons
Refrigerant Type:
R-454B
Condenser City Water:
128 GPM
Condenser Tower Water:
258 GPM
Rating Basis:
50°F leaving fluid, 115°F condensing
Process Pump & Reservoir
- Process Pump HP: 15
- Process Pump GPM: 240
- Process Pump PSI: 70
- Evaporator Pump HP: 5
- Evaporator Pump GPM: 205
- Reservoir Operating: 1,200 gallons
- Reservoir Holding: 1,475 gallons
Electrical
- Voltage: 230V / 460V / 575V
- Phase: Three Phase
- Frequency: 60 Hz
- Full Load Amps: 376.0 (230V) / 188.0 (460V) / 151.0 (575V)
Connections, Dimensions & Weight
To Process Connection:
4"
From Process Connection:
4"
Water Make-Up Connection:
1-1/2"
Overflow Connection:
4"
Condenser Connection:
4"
Height:
112"
Width:
136"
Depth:
128"
Shipping Weight:
6,300 lbs
Operating Weight:
17,500 lbs