Description
The Temptek TTI-90W is a water-cooled central chiller rated 90 tons at 50°F leaving fluid and 115°F condensing temperature, on 3 refrigeration zones. It runs 3 scroll compressors of 30 HP each on R-454B. The process pump delivers 270 GPM at 65 PSI (15 HP) from a 1,200 gallons reservoir. Condenser water is listed at 128 GPM of 60°F city water or 255 GPM of 85°F tower water. Also available: the alternate TI-90W, the same water-cooled central format and capacity class.
Product Overview
Part Number:
TTI-90W
Manufacturer:
Temptek
Configuration & Specifications
Refrigeration Zones Quantity:
3
Compressor Quantity:
3
Compressor Horsepower:
30
Compressor Type:
Scroll
Total Capacity:
90 tons
Refrigerant Type:
R-454B
Condenser City Water:
128 GPM
Condenser Tower Water:
255 GPM
Rating Basis:
50°F leaving fluid, 115°F condensing
Process Pump & Reservoir
- Process Pump HP: 15
- Process Pump GPM: 270
- Process Pump PSI: 65
- Evaporator Pump HP: 5
- Evaporator Pump GPM: 205
- Reservoir Operating: 1,200 gallons
- Reservoir Holding: 1,475 gallons
Electrical
- Voltage: 230V / 460V / 575V
- Phase: Three Phase
- Frequency: 60 Hz
- Full Load Amps: 444.0 (230V) / 222.0 (460V) / 178.0 (575V)
Connections, Dimensions & Weight
To Process Connection:
4"
From Process Connection:
4"
Water Make-Up Connection:
1-1/2"
Overflow Connection:
6"
Condenser Connection:
4"
Height:
114"
Width:
147"
Depth:
147"
Shipping Weight:
6,505 lbs
Operating Weight:
20,705 lbs