1-805-484-2992

Quotes - Sizing - Sales

NQR15

Thermal Care
Product Type Capacity Refrigerant
Portable Chiller Remote Condenser 15 Tons @ 50°F R-454B or R-410A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n NQR15 as shown on this page.

Replacement chiller for the Thermal Care NQR15

Description

The Thermal Care NQR15 is a portable chiller with a remote air-cooled condenser from the Accuchiller NQ Series. Thermal Care publishes it at 15 tons (53 kW) at 50°F leaving coolant, 95°F ambient air, with a 20 to 80°F set point range. It runs one scroll compressor, on R-454B or R-410A. It carries a 30-gallon reservoir and a 3 hp process pump rated 36 GPM at 40 PSI. Thermal Care pairs it with the KCL023 remote air-cooled condenser. Replacement: we supply the Temptek CG-20A-RC, an indoor chiller with a remote air-cooled condenser rated 18.5 tons at 50°F, against the 15 tons Thermal Care publishes for this unit at 50°F. Both makers rate at 50°F leaving fluid, so the comparison is like for like.

Product Overview

Part Number:
NQR15
Manufacturer:
Thermal Care
Replacement Unit:
Temptek CG-20A-RC

Published Capacity

Cooling Capacity:
15 tons (53 kW)
Rating Basis:
50°F leaving coolant, 95°F ambient air
Set Point Range:
20 to 80°F

Configuration & Specifications

Compressor:
Scroll
Compressors:
1
Refrigeration Circuits:
One
Refrigerant:
R-454B or R-410A
Condenser:
Remote Air-Cooled
Evaporator:
Stainless Steel Brazed Plate
Controls:
PLC, 7-inch Color Touch Screen
Sound Pressure:
73 dBA at 1 m

Pump & Reservoir

  • Reservoir: 30 gallons
  • Process Pump: 3 hp
  • Pump Flow: 36 GPM
  • Pump Pressure: 40 PSI

Electrical

  • Voltage: 460V
  • Phase: Three Phase
  • Frequency: 60 Hz
  • Minimum Circuit Ampacity: 41 A
  • Maximum Overcurrent Protection: 70 A

Connections

Process Connections:
1-1/2 in
Remote Condenser:
KCL023

Dimensions & Weight

Dimensions (L x W x H):
75 x 34 x 53 in
Shipping Weight:
1,315 lbs (596 kg)
Operating Weight:
1,500 lbs (680 kg)

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales