Replacement unit for the Thermal Care NQ Series Remote Air-Cooled

NQ Series Remote Air-Cooled

The NQ with its condenser on the roof: 5 to 40 tons of portable chiller indoors, with the heat rejected outside through a matched remote air-cooled condenser.

PRODUCT TYPE CAPACITY MODELS
Portable Chiller Remote Condenser 5 to 40 Tons 9

Specifications


Configuration & Size

Capacity:
5 to 40 Tons at 50°F
Models:
9 part numbers
Compressor:
One or two scroll
Process Flow:
13 to 92 GPM
Refrigerant:
R-454B, R-410A

Construction

  • Scroll compressors, one or two
  • Matched KCM or KCL remote condenser
  • Stainless brazed plate evaporator
  • Stainless process pump, poly reservoir
  • Low 47 or 53-inch indoor cabinet

Ratings

  • Rated at 50°F leaving coolant
  • 95°F ambient at the condenser
  • R-454B or R-410A
  • Power: 460/3/60 published

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.

NQ Remote Air-Cooled Chillers, 5 to 40 Tons

Chiller Inside, Condenser Outside

Nine models, each with a named remote condenser. Thermal Care pairs every NQR with its own air-cooled condenser, from the KCM009 on the NQR05 to the KCL056 on the NQR40. The chiller carries one or two scroll compressors, the brazed plate evaporator, reservoir and pump; the condenser carries the coil and fans.

Capacity is published at 50°F leaving coolant and 95°F ambient air at the condenser: 5 tons on the NQR05 up to 40 tons on the NQR40, on R-454B or R-410A, with a 20 to 80°F set point range.

The indoor cabinet is the water-cooled one. The NQR shares the NQW's low cabinet, 53 or 47 inches tall, its 14 to 67-gallon reservoirs and its 2 to 5 hp pumps, delivering 13 GPM at 40 PSI up to 92 GPM at 40 PSI.

The refrigerant piping is part of the job. Thermal Care lists the condenser connections for each pair, 7/8-inch inlet on the smallest up to 2-5/8 inch on the largest, and those lines run from the chiller to the roof.



central plant pump room with blue pumps, green piping and electrical panels

Indoor chiller, outdoor condenser: the heat leaves the building through a pair of refrigerant lines.

Request a Quote

NQ Series Remote Air-Cooled Applications

Molding in sealed rooms
Molding in sealed rooms
Rooftop heat rejection
Rooftop heat rejection
Packaging lines
Packaging lines
Bakery and food plants
Bakery and food plants

schematic of the NQ series Remote Air-Cooled circuit, showing where the process fluid and the condenser heat go

Line Length Is Part of the Selection

A remote-condenser chiller solves the room-heat problem of an air-cooled portable without needing a tower. The cost is the refrigerant piping: a hot-gas line out to the condenser and a liquid line back, sized for the length and the lift between them. Long runs and big vertical rises need oil traps and larger lines, and they reduce capacity if they are ignored.

Before replacing one, measure the existing line run and check whether the condenser on the roof is being kept. A condenser that has been in the weather for fifteen years is usualy replaced with the chiller, and the new pair should be selected together for the refrigerant the new unit uses. The indoor vs outdoor installation guide covers where each arrangement makes sense.

Every part-number page below names the Temptek remote-condenser unit we supply in its place, sized to cover the NQR's published 50°F capacity. The NQR40 is above the largest Temptek remote-condenser portable, so its page names a Temptek air-cooled chilling module with a remote condenser.
Call and talk it through with an engineer: 1-805-484-2992

Questions We Get on NQ Remote-Condenser Chillers

Compare the condenser's model plate with Thermal Care's pairing: the KCM009 belongs with the NQR05, the KCL023 with the NQR15, the KCL030 with the NQR20 and the KCL056 with the NQR40. A mismatch means someone has already changed one half of the pair, and the system may have been running on a condenser sized for another chiller, which can explain an old complaint of high head pressure in summer. The condenser plate also shows its age and refrigerant. Send photos of both nameplates, because the condenser for the replacement is selected around the new unit's refrigerant.

On the roof: the process load plus compressor work leaves through the refrigerant lines, at least 480,000 BTU/hr on the NQR40, 40 tons at 12,000 BTU/hr per ton. Only pump and cabinet warmth stays inside, which is why the arrangement suits sealed molding rooms and food plants. The trade is a line run sized for its length and lift, so measure that run before the quote.

Start from the KCL030's connections, 2-5/8 inch on the hot-gas inlet and 1-5/8 inch on the liquid outlet, but do not assume the field lines match them. Line size is set by run lenght and vertical lift: a long horizontal run may need a larger hot-gas line to limit pressure drop, while a tall riser needs a line small enough, or a trap, to carry oil back up. Measure the existing line sizes, the total run and the height between the chiller and the roof. A mistake here costs capacity on the new unit and can starve its compressor of oil.

A change of format: at 40 tons the NQR40 outruns the CG-40A-RC, Temptek's biggest remote-condenser portable at 36.7 tons, so we supply the MA-50-RC-C, a remote-condenser chilling module rated 46.4 tons at 50°F. That is 6.4 tons over the NQR40's rating, about 16%. Since the NQR40 is a chilling module and not a portable, ask how the reservoir and pump duty of the NQR40 is carried with it. The smaller sizes stay in the portable format, the 15-ton NQR15 going to the CG-20A-RC at 18.5 tons.

From 48 x 34 inches of floor on the NQR05 to 105 x 41 inches on the largest sizes, with 53 inches of height through the NQR15 and 47 inches from the NQR25 up. The NQR08 to NQR15 share a 75 x 34-inch footprint, and the NQR25 and larger sit on 87 or 105 by 41 inches. With the condenser fans on the roof, the cabinet is low enough for a mezzanine or a tight press aisle, and Thermal Care publishes 70 to 78 dBA at 1 meter. Leave service room on the side where the refrigerant lines leave the cabinet, since that is where the brazing happens on a swap.


NQ Remote Air-Cooled Units