1-805-484-2992

Quotes - Sizing - Sales

TCW300J

Thermal Care
Product Type Capacity Refrigerant
Central Chiller Water-Cooled Central 80 Tons @ 50°F R-513A or R-134a

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n TCW300J as shown on this page.

Replacement chiller for the Thermal Care TCW300J

Description

The Thermal Care TCW300J is a water-cooled centrifugal central chiller from the Accuchiller TC Series. Thermal Care publishes it at 80 tons (281 kW) at 50°F set point, 60°F return, 85°F condenser water, one configuration of a frame its series table lists at 30 to 90 tons, with a 40 to 75°F set point range. It runs one Turbocor centrifugal compressor, on R-513A or R-134a. Replacement: we supply the Temptek TTI-80W, a water-cooled central chiller rated 85.2 tons at 50°F, against the 80 tons Thermal Care publishes for this unit at 50°F. Both makers rate at 50°F leaving fluid, so the comparison is like for like.

Product Overview

Part Number:
TCW300J
Manufacturer:
Thermal Care
Replacement Unit:
Temptek TTI-80W

Published Capacity

Cooling Capacity:
80 tons (281 kW)
Frame Capacity Range:
30 to 90 tons
Rating Basis:
50°F set point, 60°F return, 85°F condenser water
Set Point Range:
40 to 75°F

Configuration & Specifications

Compressor:
Turbocor Centrifugal, Magnetic Bearing
Compressors:
1
Refrigeration Circuits:
One
Refrigerant:
R-513A or R-134a
Condenser:
Water-Cooled
Evaporator:
Stainless Steel Brazed Plate
Controls:
PLC

Electrical

Voltage:
460V
Phase:
Three Phase
Frequency:
60 Hz
Minimum Circuit Ampacity:
129 A
Maximum Overcurrent Protection:
225 A

Connections

Process Connections:
4 in flange
Condenser Water Connections:
4 in flange

Dimensions & Weight

Dimensions (L x W x H):
120 x 29 x 77 in
Shipping Weight:
2,100 lbs (953 kg)
Operating Weight:
2,300 lbs (1,043 kg)

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales