1-805-484-2992

Quotes - Sizing - Sales

TCW600M

Thermal Care
Product Type Capacity Refrigerant
Central Chiller Water-Cooled Central 180 Tons @ 50°F R-513A or R-134a

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n TCW600M as shown on this page.

Replacement chiller for the Thermal Care TCW600M

Description

The Thermal Care TCW600M is a water-cooled centrifugal central chiller from the Accuchiller TC Series. Thermal Care publishes it at 180 tons (633 kW) at 50°F set point, 60°F return, 85°F condenser water, one configuration of a frame its series table lists at 30 to 180 tons, with a 40 to 75°F set point range. It runs two Turbocor centrifugal compressors, on two refrigeration circuits, on R-513A or R-134a. Replacement: we supply the Temptek TTI-180W, a water-cooled central chiller rated 180 tons at 50°F, against the 180 tons Thermal Care publishes for this unit at 50°F. Both makers rate at 50°F leaving fluid, so the comparison is like for like.

Product Overview

Part Number:
TCW600M
Manufacturer:
Thermal Care
Replacement Unit:
Temptek TTI-180W

Published Capacity

Cooling Capacity:
180 tons (633 kW)
Frame Capacity Range:
30 to 180 tons
Rating Basis:
50°F set point, 60°F return, 85°F condenser water
Set Point Range:
40 to 75°F

Configuration & Specifications

Compressor:
Turbocor Centrifugal, Magnetic Bearing
Compressors:
2
Refrigeration Circuits:
Two
Refrigerant:
R-513A or R-134a
Condenser:
Water-Cooled
Evaporator:
Stainless Steel Brazed Plate
Controls:
PLC

Electrical

Voltage:
460V
Phase:
Three Phase
Frequency:
60 Hz
Minimum Circuit Ampacity:
274 A
Maximum Overcurrent Protection:
350 A

Connections

Process Connections:
6 in flange
Condenser Water Connections:
6 in flange

Dimensions & Weight

Dimensions (L x W x H):
126 x 54 x 77 in
Shipping Weight:
4,700 lbs (2,132 kg)
Operating Weight:
5,200 lbs (2,359 kg)

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales