1-805-484-2992

Quotes - Sizing - Sales

TCFW350A

Thermal Care
Product Type Capacity Refrigerant
Central Chiller Water-Cooled Central 40 to 120 Tons @ 50°F R-513A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n TCFW350A as shown on this page.

Replacement chiller for the Thermal Care TCFW350A

Description

The Thermal Care TCFW350A is a water-cooled centrifugal process chiller from the Accuchiller TCF Series. Thermal Care publishes it at 40 to 120 tons cooling water at a 50°F set point, 60°F return and 85°F condenser water, with a 40 to 75°F set point range, on one Turbocor centrifugal compressor, a hybrid film evaporator and R-513A. Replacement: we supply the Temptek TTI-120WD, a water-cooled central chiller rated 120 tons at 50°F, against the top of the 40 to 120-ton range Thermal Care publishes for this model at 50°F. Both makers rate at 50°F leaving fluid, so the comparison is like for like.

Product Overview

Part Number:
TCFW350A
Manufacturer:
Thermal Care
Replacement Unit:
Temptek TTI-120WD

Published Capacity

Cooling Capacity:
40 to 120 tons
Rating Basis:
50°F set point, 60°F return, 85°F condenser water
Set Point Range:
40 to 75°F
Intended Operating Range:
40 to 75°F
Process Fluid:
Water
Evaporator Flow:
240 GPM at 50°F

Configuration & Specifications

Compressor:
Turbocor Variable-Speed Centrifugal
Compressors:
1
Refrigeration Circuits:
One
Refrigerant:
R-513A
Condenser:
Water-Cooled
Evaporator:
Hybrid Film
Controls:
PLC

Electrical

Voltage:
460V / 575V
Phase:
Three Phase
Frequency:
60 Hz
Minimum Circuit Ampacity:
229 A (460V) / 184 A (575V)
Maximum Overcurrent Protection:
400 A (460V) / 300 A (575V)

Dimensions & Weight

Shipping Weight:
3,400 lbs (1,542 kg)
Operating Weight:
3,800 lbs (1,724 kg)

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.