A Turbocor compressor on a hybrid film evaporator: Thermal Care's TCF line, one 40 to 120-ton process chiller and one 13°F ice-rink chiller.
| PRODUCT | TYPE | CAPACITY | MODELS |
|---|---|---|---|
| Central Chiller | Centrifugal Central | 45 to 120 Tons | 2 |
Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.
Two models, one circuit each. The TCFW350A is a water-cooled process chiller, and the TCFW375 a water-cooled chiller built for ice rinks. Both carry a single Turbocor variable-speed centrifugal compressor on R-513A.
The evaporator is what is different. Thermal Care pairs the compressor with a hybrid film evaporator, which it describes as giving the most efficient heat transfer while minimizing the refrigerant charge.
The TCFW350A is published at 40 to 120 tons cooling water at a 50°F set point, 60°F return and 85°F condenser water, with a 40 to 75°F set point range and 240 GPM of evaporator flow at 50°F.
The TCFW375 is published at 45 to 55 tons on 40% ethylene glycol at a 13°F set point and 16°F return, with a 10 to 55°F set point range and an intended operating range of 10 to 15°F.
Hybrid film evaporator, magnetic-bearing compressor, R-513A: two chillers built around the same pairing.
Request a Quote
The two TCF models look alike and do opposite jobs. The TCFW350A makes chilled water in the 40s and 50s for a plant header, the duty a Turbocor does best. The TCFW375 pulls glycol down to 13°F for an ice sheet, which is why it is rated on 40% ethylene glycol and why its capacity, 45 to 55 tons, is so much lower for a similar compressor.
An ice rink is also an unusual load: the brine loop runs cold for months, the heat load swings with the crowd and the resurfacing schedule, and the condenser heat is often recovered to melt snow or heat water. The glycol type and mix guide covers what a 40% mix does to flow and pump selection.
The TCFW350A page names the Temptek water-cooled central chiller we supply in its place, sized to cover the top of its published 120-ton range at 50°F. Nothing we supply is rated at the TCFW375's 10 to 15°F duty, since Temptek's range ends near 20°F, so its page sends you to an application specialist.