Replacement unit for the Trane CGAM Series

CGAM Series

Trane's air-cooled scroll chiller: the CGAM, 20 to 130 nominal tons, with a low-temperature process option down to 10°F on glycol.

PRODUCT TYPE CAPACITY MODELS
Air-Cooled Scroll Chiller Packaged, Air-Cooled 20 to 130 nominal tons 14

Specifications


Configuration & Size

Capacity:
20 to 130 nominal tons
Models:
14 part numbers
Refrigerant:
R-454B
Circuits:
1 to 35 tons, 2 from 40 tons
Supply:
200 to 575 V, 60 Hz

Construction

  • Scroll compressors, one or two circuits
  • Round tube and plate fin condenser
  • Optional dual pump package and buffer tank
  • Symbio 800 controller
  • R-454B refrigerant

Ratings

  • AHRI 550/590 nominal size
  • Standard leaving fluid 40 to 65°F
  • Process option 10 to 40°F
  • Ambient to 125°F

Specifications sourced from Trane's published product catalogs CG-PRC017AA-EN and AC-PRC002K-EN (tranetechnologies.com), October 2026. Trane, CGAM, Ascend and Symbio are trademarks of Trane Technologies; referenced here for cross-reference only. Sizes are Trane's nominal tons; rated performance comes from Trane's selection data. Confirm against the unit nameplate before ordering.

CGAM, 20 to 130 Nominal Tons

Fourteen Sizes, One or Two Circuits

Fourteen sizes. 20, 26, 30 and 35 tons on one circuit with two compressors; 40 to 120 tons on two circuits with four; the 130 with six.

Process range. Standard units deliver 40 to 65°F; the low-temperature processing option covers 10 to 40°F with glycol. The Temptek line we supply holds leaving fluid down to about 20°F, so a CGAM run on that option below 20°F is rated separately rather than read from the part-number match.

Pump package and tank. An optional dual pump package of 5 to 15 HP and a buffer tank of 140 to 195 gallons mount inside the frame.

Wide ambient. Starts and runs from 0°F with the wide-ambient option, to 125°F with high ambient, and to -20°F with extreme low.



storage bins of small parts on shelving

Scroll compressors, an evaporator and round tube and plate fin condenser coils, with an optional pump package and buffer tank.

Request a Quote

CGAM Series Applications

Chilled water
Chilled water
Plastics molding
Plastics molding
Brewery glycol
Brewery glycol
Outdoor pads
Outdoor pads

schematic of the CGAM series circuit, showing where the process fluid and the condenser heat go

A Comfort Chiller on a Process Loop

The CGAM is sized at 44°F leaving water. On a 28°F brewery glycol loop the same machine makes far less than its nominal tons, and Trane requires glycol for anything below 42°F. Check which evaporator application the unit was built for before matching tons. The leaving fluid temperature guide shows how capacity falls with set point.

Every part-number page below names the Temptek unit we supply in its place, sized from Trane's nominal tons on Temptek's 0.80 multiplier at 40°F, or points to the add-on module range where the size is past a single chiller.
Call and talk it through with an engineer: 1-805-484-2992

Trane CGAM Chillers: Set Point and Sizing Questions

Because it has the least room of the three: the CGAM060's 60 nominal tons, taken through Temptek's 0.80 factor, ask for a 50°F rating of 75 tons, and the TTOACS-80D-MZC-2P we supply makes 75.8. The CGAM020 needs 25 tons and gets the TTOACS-30S-CG-1P at 28.8, and the CGAM130 needs 162.5 and gets the TTOACS-190D-MZC-2P at 170.1. A match under 1 ton holds at 40°F and warmer, but leaves nothing for a colder set point or for load added since the Trane went in. If either applies to a CGAM060 duty, say so, and that pick gets a call for rating at your actual conditions.

Only if the old unit had them, and both are checked against the loop rather than copied across. Trane's dual pump package runs 5 to 15 HP; on the CGAM060 it is 7.5 HP with 76.7 ft of available head, which tells you the pressure drop the plant piping was designed around. The buffer tank, 140 to 195 gallons inside the frame, adds loop volume that steadies a small or fast-changing load. Remove it without replacing the volume and a short loop can make the new chiller cycle. Note on the request whether your CGAM has either option and the head its pump makes today.

The nominal tons stop being a useful guide. A CGAM with that option was built for 10 to 40°F on glycol, but its nominal size is still a 44°F figure, so at a 25°F set point it was delivering well under the badge. Temptek's published 0.80 multiplier covers 40°F; below that we call for rating at your set point and mix rather than stretch the multiplier. Give us the temperature the unit actually holds, the glycol type and percentage, and if possible the flow and temperature drop at peak, so the replacement is sized from the duty instead of the label.

All of the cooling: the 20, 26, 30 and 35-ton sizes run two compressors on a single refrigerant circuit, so a fault on that circuit takes the whole chiller down. The 40 to 120-ton sizes split four compressors over two circuits and the CGAM130 carries six, so they can keep part of their capacity through a circuit failure. If your process has relied on a two-circuit CGAM to keep running at about half capacity, tell us, because that redundancy has to be kept deliberately in the replacement. If the old unit was single-circuit and the plant can no longer tolerate a full stop, the swap is the moment to change that.

Because the option shows the outdoor conditions the plant actually asked the chiller to work in. Trane's wide-ambient build starts from 0°F, the high-ambient build runs from 32°F up to 125°F, and the extreme-low option reaches -20°F. A CGAM fitted with extreme low was most likely carrying process load through winter, and its glycol mix had to protect the loop at that air temperature. Tell us the coldest and hottest air the pad sees, so the replacement covers both ends.