York
Product Type Capacity Refrigerant
Air-Cooled Scroll Chiller Air-Cooled 175.3 Tons nominal R-410A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n YLAA0175HE as shown on this page.

Replacement chiller for the York YLAA0175HE

Description

The York YLAA0175HE is a high efficiency YLAA Style B air-cooled scroll chiller on R-410A, with 6 scroll compressors on two refrigerant circuits and a brazed plate evaporator. Johnson Controls lists a nominal rating of 175.3 tons at 214.7 kW input, an EER of 9.8 and an IPLV of 16.2. It is 232.7 inches long and weighs 8,001 lb operating. Replacement: no single Temptek unit reaches 219.12 tons, so we supply it from our sister line: add-on chiller modules for plant-wide systems to 300 tons, paired to the load.

Product Overview

Part Number:
YLAA0175HE
Manufacturer:
York
Series:
YLAA Series

Published Capacity

Nominal Rating:
175.3 tons
Input Power:
214.7 kW
EER:
9.8
IPLV:
16.2
Rating Basis:
AHRI Standard 550/590
Leaving Liquid:
40 to 55°F standard; to 10°F with the low temperature glycol kit
Air on Condenser:
-10 to 125°F (low ambient kit below 30°F)

Configuration & Specifications

Compressors:
6 hermetic scroll (3/3 per circuit)
Nominal Tons per Compressor:
Circuit 1: 32; circuit 2: 32
Refrigerant Circuits:
2
Refrigerant:
R-410A
Refrigerant Charge (circuit 1 / 2):
94/92 lb
Condenser Fans (circuit 1 / 2):
5/5, 2 HP
Total Airflow:
150,000 cfm

Evaporator

Type:
Brazed plate
Water Volume:
14.3 gallons
Minimum Water Flow:
150 GPM
Maximum Water Flow:
625 GPM
Max Water Side Pressure:
150 psig

Electrical

Voltages Offered:
200, 230, 380, 460 or 575 V / 3 phase / 60 Hz

Connections

Water Connections:
4 in (side extension kit; evaporator nozzle 3 in)

Dimensions & Weight

Length:
232.7 in
Width:
88 in
Height:
94.2 in
Shipping Weight:
7,882 lb
Operating Weight:
8,001 lb

Specifications sourced from Johnson Controls' published YLAA engineering guide, Form 150.72-EG6 (docs.johnsoncontrols.com), October 2026. York and YLAA are trademarks of Johnson Controls; referenced here for cross-reference only. Capacities are the guide's nominal ratings under AHRI 550/590. Confirm against the unit nameplate before ordering.