| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Air-Cooled Scroll Chiller | Air-Cooled | 146.9 Tons nominal | R-410A |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n YLAA0156HE as shown on this page.
The York YLAA0156HE is a high efficiency YLAA Style B air-cooled scroll chiller on R-410A, with 5 scroll compressors on two refrigerant circuits and a brazed plate evaporator. Johnson Controls lists a nominal rating of 146.9 tons at 172.8 kW input, an EER of 10.2 and an IPLV of 16.1. It is 232.7 inches long and weighs 7,428 lb operating. Replacement: we supply the Temptek TTOACS-210D-MZC-2P, an outdoor air-cooled packaged chiller rated 188 tons at 50°F, against the 146.9 tons York publishes for this unit at its nominal AHRI rating (44°F leaving water). Temptek rates at 50°F, so the 44°F figure is matched on Temptek's published 40°F capacity multiplier of 0.80, which leaves the pick some margin; we confirm it at your set point.
Specifications sourced from Johnson Controls' published YLAA engineering guide, Form 150.72-EG6 (docs.johnsoncontrols.com), October 2026. York and YLAA are trademarks of Johnson Controls; referenced here for cross-reference only. Capacities are the guide's nominal ratings under AHRI 550/590. Confirm against the unit nameplate before ordering.