| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Packaged Chiller | Water-Cooled Packaged | 29.2 Tons @ 50°F | R407C or R404A |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PWC360D as shown on this page.
The Drake PWC360D is a 30 hp dual-circuit scroll packaged water-cooled chiller, from the PWC / PWCT Scroll line. Drake publishes a capacity table for it rather than a single rating: 29.2 tons at 50°F leaving fluid and 105°F condensing temperature on R407C, at an EER of 13.9. The same column runs from 21.1 tons at 35°F to 39.4 tons at 65°F. It is offered on R407C for a 25°F to 55°F suction range and R404A for a -10°F to 45°F suction range. Drake lists two ZB114KCE compressors of 15 hp each. Replacement: we supply the Temptek CG-30W, a water-cooled portable chiller rated 30 tons at 50°F, against the 29.2 tons Drake publishes for this unit at 50°F leaving fluid and 105°F condensing temperature on R407C. Drake rates this water-cooled table by condensing temperature rather than water temperature; the 105°F column is the usual condensing point on 85°F tower water, and we confirm it with your water temperature.
Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.