| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Glycol Chiller | Air-Cooled Packaged | 37.5 Tons @ 30°F | Not published |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PB230F14R4CL-A-V as shown on this page.
The PRO PB230F14R4CL-A-V is a 60 hp packaged glycol chiller from PRO's legacy Classic line, on two compressors of 30 hp each. PRO's legacy table lists estimated capacity at 90°F ambient: 398,200 Btu/h at 25°F, 450,000 Btu/h at 30°F, 506,000 Btu/h at 35°F leaving fluid. Its circulation pumping is two 3 HP, with two 2 in glycol field connections. Replacement: we supply the Temptek TTOACS-80D-MZC-2P, an outdoor air-cooled packaged chiller rated 75.8 tons at 50°F, against the 37.5 tons PRO Refrigeration publishes for this unit at 30°F leaving glycol and 90°F ambient. PRO publishes no 50°F rating. Temptek's published capacity multiplier at a 30°F set point is 0.60 of its 50°F rating, so the pick is sized at PRO's 30°F figure divided by 0.60, and confirmed at your set point before quoting. Divided by 0.60, the 37.5 tons call for at least 62.5 tons of Temptek 50°F rating.
Specifications sourced from PRO Refrigeration's published chiller data sheets, series one-sheets and legacy specification tables (prochiller.com), October 2026. PRO Refrigeration, PRO Chiller Systems, Chill&Flow, ChilStar, PRO4, V Piston, V-Scroll, Revolution, PROGreen and PROElliot are trademarks of their owner; referenced here for cross-reference only. PRO publishes these as estimated capacities. Confirm against the unit nameplate before ordering.