Replacement unit for the PRO Refrigeration Classic Series

Classic Series

PRO's legacy Classic chillers: one or two compressors, 10 to 100 hp, in a coated steel frame.

PRODUCT TYPE CAPACITY MODELS
Glycol Chiller Packaged, Legacy 10 to 100 HP 10

Specifications


Configuration & Size

Capacity:
89,500 to 798,000 Btu/h at 30°F
Models:
10 part numbers
Compressors:
1 x 10 to 2 x 50 hp
Pumps:
1 or 2 circulation
Weight:
2,300 to 8,200 lbs

Construction

  • One or two compressors
  • Coated steel frame
  • Galvanized sheet metal housing
  • 2 to 5 hp circulation pumps
  • 2-inch glycol connections

Ratings

  • Rated at 25 to 35°F glycol
  • 90°F ambient
  • Refrigerant not listed
  • 230 or 460 V three-phase

Specifications sourced from PRO Refrigeration's published chiller data sheets, series one-sheets and legacy specification tables (prochiller.com), October 2026. PRO Refrigeration, PRO Chiller Systems, Chill&Flow, ChilStar, PRO4, V Piston, V-Scroll, Revolution, PROGreen and PROElliot are trademarks of their owner; referenced here for cross-reference only. PRO publishes these as estimated capacities. Confirm against the unit nameplate before ordering.

Classic Series, 10 to 100 HP

One Compressor or Two

Ten models. Five single-compressor units from 10 to 50 hp (PB110 to PB150) and five dual-compressor units from 2 x 10 to 2 x 50 hp (PB210 to PB250).

Capacity at the glycol temperature. From 89,500 Btu/h at 30°F on the PB110 to 798,000 Btu/h on the PB250, at 90°F ambient, with 25 and 35°F figures.

Pumps grow with the frame. One 2 to 5 hp circulation pump on the single-compressor units, two on most dual-compressor units.

Electrical on 230 or 460 V. From 70 A MCA at 230/3 on the 10 hp unit to 477 A on the 100 hp.



the inside of a commercial walk-in cooler

One or two compressors, circulation pumping and 2-inch glycol connections in a coated steel frame.

Request a Quote

Classic Series Applications

Brewery fermentation
Brewery fermentation
Winery fermentation
Winery fermentation
Dairy processing
Dairy processing
Outdoor pads
Outdoor pads

schematic of the Classic series circuit, showing where the process fluid and the condenser heat go

From a Published Legacy Table

PRO publishes the Classic table on its Legacy Chillers page as an image, and the figures here are read from it; it lists no tank size or refrigerant. Check the nameplate.

Every part-number page below names the Temptek unit we supply in its place, sized from PRO's 30°F figure on Temptek's published multiplier: a Temptek unit makes 0.60 of its 50°F rating at a 30°F set point, so the pick is the PRO figure divided by 0.60.
Call and talk it through with an engineer: 1-805-484-2992

Questions We Get on the PRO Classic Series

Use the 25°F column only for the PRO side of the comparison; the Temptek pick is built on the 30°F figure. A cellar held at 25°F can see what its old Classic made there, which is less than the 30°F number. The 0.60 multiplier belongs to a 30°F set point, so a 25°F duty needs its own rating rather than a stretch of that division. Tell us the set point you hold, and the unit is rerated there before it is quoted.

Its requirement, 110.83 tons on Temptek's 50°F basis, sits just above the 110.1 tons that unit is rated for. PRO lists the 100 hp unit at 798,000 Btu/h at 30°F, or 66.5 tons; worked back to 30°F, the 120D would make about 66.06 tons, roughly 5,300 Btu/h below the Classic. That looks like a rounding error on paper and shows up as a loop that drifts warm on the hottest afternoon of the year. So the PB250 goes to the TTOACS-150D-MZC-2P at 145.8 tons. If the plant's measured load is well below what the PB250 was rated for, send the logged data and we will look at whether the smaller unit is defensible.

The TTOACS-25S-CG-1P, which carries a 24.2-ton rating at 50°F. PRO lists the PB120F5R4CL-A-V at 148,000 Btu/h, 12.33 tons, at 30°F glycol and 90°F air, so the pick needs at least 20.55 tons on Temptek's 50°F basis. At 30°F the 25S works out to about 14.5 tons, a little over two tons above the Classic, a sensible reserve for an older plant whose load has crept up. The single-compressor PB110 below it, at 89,500 Btu/h or 7.46 tons, needs 12.43 tons and lands on the TTOACS-15S-CG-1P at 14.4.

No, the pick is made on tons, so the standby value of a second compressor has to be asked for. The 80 hp PB240F20R4CL-A-V is published at 54.5 tons at 30°F, so it calls for 90.83 tons and is matched by the 110.1-ton TTOACS-120D-MZC-2P; the PB210 and PB220 size in to the TTOACS-30S-CG-1P and TTOACS-50S-CG-1P. On a dual Classic, one compressor tripping leaves roughly half the plant running, and many breweries have relied on that for years without ever writing it down. If losing a compressor must not cost you a crash, say so on the quote request, so the replacement is laid out for it and not just sized.

About half as much at 460 V on PRO's figures: 70 A MCA at 230/3 against 35 A at 460/3 on the 10 hp unit, and 477 A against 239 A on the 100 hp. Those numbers describe the old chiller only. The unit we supply carries it's own MCA and maximum overcurrent rating, so the disconnect, conductors and breaker are checked against its nameplate, not reused on the assumption that a similar tonnage draws a similar current.