Replacement unit for the Cold Shot CSAC Series

CSAC Series

Cold Shot's CSAC line starts where the others do not: a 1/4-ton unit on 120 V, and on through the sizes to a 100-ton dual-pump portable.

PRODUCT TYPE CAPACITY MODELS
Portable Chiller Air-Cooled Portable 1/4 to 100 Tons 24

Specifications


Configuration & Size

Capacity:
1/4 to 100 tons at 50°F
Models:
24 part numbers
Frames:
B, C and D
Process Pump:
3/4 to 10 hp
Refrigerant:
Not listed

Construction

  • Air-cooled condenser
  • Process pump on portable models
  • B, C and D frames
  • DM and DP pump packages
  • ST stationary at 1.5 and 40 tons

Ratings

  • Rated at 50°F leaving fluid
  • 95°F ambient air
  • Refrigerant not listed
  • 120 V to 460 V by size

Specifications sourced from Cold Shot Chillers' published Chiller Specifications page, per-size chiller pages and EZ Chiller page (waterchillers.com), September 2026. Cold Shot Chillers, EZ Chiller and Guardian are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.

CSAC Series Air-Cooled Chillers, 1/4 to 100 Tons

From the Benchtop to the Plant

Twenty-four models on three frames. The B frame covers 1/4 to 1 ton, the C frame 1.5 to 5 tons and the D frame 10 to 100 tons, with DM units at 2 and 7.5 tons, DP pump packages from 25 tons, an unlettered CSAC-360, one stationary unit at 40 tons, and the 1.5-ton unit in portable, reverse flow, continuous flow and stationary versions.

Capacity is published at 50°F leaving fluid and 95°F ambient, from 3,000 Btu/h on the CSAC-003-B to 1,200,000 Btu/h on the CSAC-1200-D-DP. The CSAC rows list no refrigerant.

The small units plug in. The CSAC-003-B to CSAC-009-B are listed on 120 V single-phase as well as 230 V, with a 3/4 hp pump for 10 GPM at 30 PSI; the 1-ton moves to 230 V single-phase or 230 and 460 V three-phase.

The top of the line is 460 V only. The CSAC-1200-D-DP is listed on 460 V three-phase with a 10 hp pump for 225 GPM at 30 PSI and 4-inch 150# flanges.



blue-toned bottling and canning line with bottles on conveyors

An air-cooled circuit and a process pump, sized from a lab instrument to a plant header.

Request a Quote

CSAC Series Applications

Lasers and optics
Lasers and optics
Lab instruments
Lab instruments
Machine spindles
Machine spindles
Molding presses
Molding presses

schematic of the CSAC series circuit, showing where the process fluid and the condenser heat go

Small Loads Are Flow Problems

A quarter-ton chiller on a laser or an analytical instrument rarely fails on heat load; it fails on flow and pressure at the load's inlet. The CSAC fractional units list a 3/4 hp pump rated 10 GPM at 30 PSI, which suits a short hose run to one instrument. The instrument's own manual usually gives the flow and inlet pressure it needs, and that is the number to match first.

At the other end of the line, a 100-ton air-cooled portable indoors rejects well over a million Btu/h in to the building. The glycol chiller sizing guide works the load either way, from flow and temperature rise.

Every part-number page below names the Temptek unit we supply in its place, sized to cover the published 50°F capacity: a Temptek CF fractional-ton unit to 1.5 tons, a CG air-cooled portable to 25 tons, and a TTI air-cooled central chiller above.
Call and talk it through with an engineer: 1-805-484-2992

CSAC Series: Frames, Voltage and Pump Flow

For heat, yes: at 10 GPM the 3,000 Btu/h CSAC-003-B warms the water only about 0.6°F across the load. Even the CSAC-009-B at 9,000 Btu/h sees just 1.8°F of rise at the same flow. The pump is sized for pressure, not heat, because small instruments and laser heads have narrow internal passages and quick-connect fittings that need real pressure to pass any useful flow. The common mistake is matching the replacement on tons and accepting whatever pump comes with it; the instrument then alarms on low flow. Give us the flow and inlet pressure the instrument maker requires.

It moves 225 GPM through 4-inch 150# flanges, and at full output that flow comes back about 10.7°F warmer than it left, the rating spread over 500 times 225 GPM on water. The 10 hp pump is rated at 30 PSI, which has to cover the header, the branch piping and the hardest-to-reach load. A plant that has teed new machines onto an undersized header often finds the far press starving while the near one floods, so check the header before taking the unit's flow as given. On glycol the rise is slightly larger at the same flow. This size is also listed on 460 V three-phase only, so the replacement goes on a 460 V feed unless you tell us otherwise.

Because the pick has to cover the full 10-ton, 120,000 Btu/h rating at 50°F, and the Temptek CG-15AF at 14.5 tons is the unit named for it, leaving about 45 percent headroom. That headroom is not wasted. It leaves space for a glycol mix or a set point below 50°F, and for a press added later. Elsewhere in the line the steps are closer: the 1-ton CSAC-012-B maps to the Temptek CF-1A, and the 40-ton CSAC-480-D-DP to the TTI-40A central chiller. If you know the 10-ton unit runs well below its rating, send the measured flow and temperature rise and we look at the selection again.

Cold Shot's table lists it with the same 1 hp, 30 GPM pump as the other 1.5-ton CSAC units, even though ST is its stationary designation, and the table does not explain the conflict. We show the pump as published and flag it. It matters in a replacement: a stationary unit depends on a pump outside the chiller, while the Temptek pick at 1.5 tons is a CF fractional-ton unit. If the old unit has no pump, the plant pump may come out or stay as a booster; if it has one, the loop was probably built around 30 GPM. Look inside the cabinet, or send a photo of the nameplate and the piping at the unit.